CIAT PRO-DIALOG+ Instruction Manual Download Page 4

1 - SAFETY CONSIDERATIONS

1.1 - General

Installation, start-up and servicing of equipment can be hazardous 
if certain factors particular to the installation are not considered: 
operating pressures, presence of electrical components and volt-
ages and the installation site (elevated plinths and built-up struc-

tures). Only properly qualified installation engineers and highly 
qualified installers and technicians, fully trained for the product, 

are authorised to install and start-up the equipment safely. Dur-
ing all servicing operations all instructions and recommendations 
which appear in the installation and service instructions for the 

product, as well as on tags and labels fixed to the equipment and 

components and accompanying parts supplied separately, must 
be read, understood and followed.

•  

Apply all standard safety codes and practices.

•  

Wear safety glasses and gloves.

•  

Use the proper tools to move heavy objects. Move units 
carefully and set them down gently.

1.2 - Avoid electrocution

Only  personnel  qualified  in  accordance  with  IEC  (International 

Electrotechnical Commission) recommendations may be permitted 
access to electrical components. It is particularly recommended 
that all sources of electricity to the unit be shut off before any work 
is begun. Shut off the main power supply at the main circuit breaker 
or isolator.

IMPORTANT: This equipment conforms to all applicable 
codes regarding electromagnetic compatibility.

2 - GENERAL DESCRIPTION

2.1 - General

Pro-Dialog is an electronic control system to regulate units of 
the following types:

• 

air-cooled liquid chillers

• 

reversible heat pumps. 

These units have one or two refrigerant circuits.

Pro-Dialog controls:

• 

compressor start-up to control the water loop

• 

the fans to optimise operation of each refrigerant circuit

• 

the defrost cycles to ensure the operation of the 
refrigerant circuits (reversible heat pumps only).

As standard Pro-Dialog offers three on/off commands:

• 

Local - on/off command using the keyboard

•  

Remote - wired on/off command using volt-free contacts

•  

Network - proprietary protocol on/off command.

The command type is selected in advance by keyboard.

2.2 - Abbreviations used

In this manual, the refrigerant circuits are called circuit A and 
circuit B. The compressors in circuit A are labelled A1, A2 and 
A3. Those in circuit B are B1 and B2.

The following abbreviations are used frequently:
LED 

Light Emitting Diode

LEN 

Internal communication bus linking the main board to  

 

the slave boards

SCT 

Saturated condensing temperature

SST 

Saturated suction temperature

EXV 

Electronic expansion valve

PD-AUX  Auxiliary input/output board

 

EREBA ACCESS 

 EN - 2 

Summary of Contents for PRO-DIALOG+

Page 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Page 2: ......

Page 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Page 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Page 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Page 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Page 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Page 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Page 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Page 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Page 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Page 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Page 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Page 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Page 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Page 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Page 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Page 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Page 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Page 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Page 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Page 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Page 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Page 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Page 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Page 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...

Page 27: ......

Page 28: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Reviews: