CIAT PRO-DIALOG+ Instruction Manual Download Page 26

6.4 - Alarm codes (cont.)

Alarm 
No.

Alarm 
code

Alarm description

Reset type

Probable cause

Action taken by the 
control

Process faults (cont.)

33

P-29

Communication loss with the 

System Manager

Automatic when communication is 

re-established

Installation bus defective

Unit goes into autonomous 

mode

34

P-30

Communication loss between 

master and slave

Automatic when communication is 

re-established

Installation bus defective

As above

35

MC-nn

Master chiller 1 configuration error 

Automatic when the master 

configuration returns to normal or 

when the unit is no longer in master/

slave mode

Master/slave configuration error

Master/slave mode is stopped

36

FC-n0

No factory configuration

Automatic when the configuration is 

entered

The unit size has not been 

configured

Unit is shut down

37

FC-01

Illegal factory configuration number

Manual

The unit size has been configured 

with the wrong value

As above

38

P-31

Network emergency stop

Manual

Network command

As above

39

P-32

Fault water pump 1

Manual

Pump overheating or poor pump 

connection

Unit is completely stopped if 

there is no emergency pump

40

P-33

Fault water pump 2

Manual

As above

As above

41

P-37

Repeated high pressure unloading, 

circuit A

Automatic

Transducer defective or fan circuit 

fault

None

42

P-38

Repeated high pressure unloading, 

circuit B

Automatic

As above

As above

43

P-40

Repeated low suction temperature 

unloading in heating mode, circuit A 

Manual

Pressure sensor defective or 

refrigerant charge too low

Circuit is shut down

44

P-41

Repeated low suction temperature 

unloading in heating mode, circuit B

Manual

As above

As above

45

P-43

Heat exchanger temperature too low, 

less than 10°C, prevents unit start-up

Automatic when the temperature 

detected returns to normal or when 

the mode returns to cooling

Operating compressor protection out 

of range or pressure sensor fault

The unit cannot start

46

P-97

Reversed entering/leaving water 

sensors

Manual

Sensor defective, sensors reversed

Unit is shut down

48

V0-xx

Fault, variable fan speed controller, 

circuit A

Manual or automatic

Speed controller fault or alert

Alert: The circuit continues to 

operate, the speed controller 

slows down the motor.

Alarm: The circuit shuts down.

49

V1-xx

Fault, variable fan speed controller, 

circuit B

As above

As above

As above

50

V3-xx

Fault, variable water pump controller

51

Sr-00

Maintenance service alert

Manual

The preventive maintenance date 

has passed

53

P62-2

Water loop control fault, missing 

sensor calibration

Automatic if the calibration is valid

No calibration

P62-3

Water loop control fault, suction 

pressure too low

Automatic the first time, if the water 

system is supplied with water, the 

second time manual if it is the same 

day

Too little water in the system

Unit is shut down

P62-4

Water loop control fault, water pump 

has not started

P62-5

Reserved

P62-6

Water loop control fault, water pump 

overload

Automatic

Missing pressure head at the water 

pump

Unit is shut down

P62-7

Water loop control fault, water flow 

rate fault

Manual

Serious water leak, casse pompe

Unit is shut down

P62-8

Water loop control fault, water 

pressure sensors mixed up

Automatic

Sensors mixed up

Unit is shut down

54

P-63

High pressure fault in circuit A

Manual

Fan fault

Circuit is shut down 

55

P-64

High pressure fault in circuit B

As above

As above

As above

56

P-99

Refrigerant leak detected

Automatic

Refrigerant leak or solvent present 

in the machine atmosphere

No action

6 - DIAGNOSTICS - TROUBLESHOOTING

 

EREBA ACCESS 

 EN - 24 

Summary of Contents for PRO-DIALOG+

Page 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Page 2: ......

Page 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Page 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Page 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Page 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Page 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Page 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Page 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Page 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Page 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Page 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Page 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Page 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Page 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Page 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Page 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Page 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Page 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Page 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Page 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Page 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Page 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Page 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Page 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Page 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...

Page 27: ......

Page 28: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Reviews: