17
HYDROCIA
T L
W
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 18.752 B
Water chillers
Heat pump
t
echnical
chaRacteRistics
s
tanDaRD
Units
foR
high
conDensing
tempeRatURes
LW ST + High condensing option
708 858 1008 1300 1302 1500 1508 1900 2100 2300
Oil
SW220
Circuit A
l
23,5
23,5
23,5
32
32
32
32
36
36
36
Capacity control
Connect Touch, electronic expansion valves (EXV)
Minimum capacity
(4)
%
30
30
30
30
30
30
30
15
15
15
Evaporator
Shell and tube flooded type
Net water volume
l
50
56
61
70
70
70
70
109
109
109
Water connections (Victaulic)
in
5
5
5
5
5
5
5
6
6
6
Drain and vent connections (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Condenser
Shell and tube type
Net water volume
l
55
55
55
76
76
76
76
109
109
109
Water connections (Victaulic)
in
5
5
5
5
5
5
5
6
6
6
Drain and vent connections (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
(4) Minimum unit capacity corresponds to a physical state of the unit and is given for indication only. The actual capacity at this stage depends on operating conditions.