HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 18.752 B
Water chillers
Heat pump
HYDROCIAT LW
t
echnical
chaRacteRistics
s
tanDaRD
Units
foR
high
conDensing
tempeRatURes
*
In accordance with standard EN14511-3:2013.
**
In accordance with standard EN14825:2016, average climate
HW1
Heating mode conditions: Evaporator entering/leaving water temperature 10°C/7°C, condenser entering/leaving water temperature
30°C/35°C, evaporator and condenser fouling factor 0 m
2
. k/W
HW2
Heating mode conditions: Evaporator entering/leaving water temperature 10°C/7°C, condenser entering/leaving water temperature
40°C/45°C, evaporator and condenser fouling factor 0 m
2
. k/W
HW3
Heating mode conditions: Evaporator entering/leaving water temperature 10°C/7°C, condenser entering/leaving water temperature
47°C/55°C, evaporator and condenser fouling factor 0 m
2
. k/W
CW1
Cooling mode conditions: Evaporator water entering/leaving temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C,
evaporator and condenser fouling factor 0 m
2
.K/W
Ƞs heat
30/35°C
& SCOP
30/35°C
Values calculated in accordance with EN14825:2016
Ƞs heat
47/55°C
& SCOP
47/55°C
Values calculated in accordance with EN14825:2016
Ƞs cool
12/7°C
& SEER
12/7°C
Bold values compliant to Ecodesign regulation: (EU) No 2016/2281 for Comfort application
SEPR
12/7°C
Values calculated in accordance with EN14825:2016
IPLV.SI
Calculations according to standard performances AHRI 551-591 (SI)
NA
Non Authorized for the specific application for CEE market
(1)
In dB ref=10
-12
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of
+/-3dB(A)). Measured in accordance with ISO 9614-1 and certified by Eurovent.
(2)
In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of
+/-3dB(A)). For information, calculated from the sound power level Lw(A).
(3)
Weight shown is guideline only. Please refer to the unit nameplate
Eurovent certified values
LW ST + High condensing option
708 858 1008 1300 1302 1500 1508 1900 2100 2300
Heating
Unit with high
condensing option
Full load performances*
HW1
Nominal capacity
kW
334
373
421
511
542
607
626
769
847
890
COP
kW/kW
5,59
5,59
5,54
5,22
5,47
5,36
5,48
5,39
5,38
5,3
HW2
Nominal heating capacity
kW
325
362
408
478
506
566
606
716
789
829
COP
kW/kW
4,62
4,59
4,55
4,29
4,50
4,43
4,54
4,45
4,45
4,41
HW3
Nominal capacity
kW
316
352
396
446
471
527
587
665
734
773
COP
kW/kW
3,85
3,83
3,79
3,50
3,68
3,63
3,78
3,65
3,65
3,63
Unit with high
condensing option
Seasonal energy efficiency**
HW1
SCOP
30/35°C
kWh/kWh
5,81
5,93
5,89
5,57
5,70
5,69
5,62
5,53
5,57
5,30
ŋs heat
30/35°C
%
224
229
227
215
220
220
217
213
215
204
HW3
SCOP
47/55°C
kWh/kWh
4,56
4,61
4,55
4,20
4,37
4,41
4,42
4,24
4,31
4,46
ŋ
s heat
47/55°C
%
174
176
174
160
167
169
169
162
164
170
P
rated
kW
416
419
473
540
571
638
700
807
890
936
Cooling
Unit with high
condensing option
Full load performances*
CW1
Nominal capacity
kW
282
313
352
NA
NA
NA
NA
NA
NA
NA
EER
kW/kW
4,89
4,87
4,82
NA
NA
NA
NA
NA
NA
NA
Eurovent class
-
B
B
B
NA
NA
NA
NA
NA
NA
NA
Unit with high
condensing option
Seasonal energy efficiency**
SEER
12/7°C
Comfort low temp. kWh/kWh 5,76 5,83 5,80
NA
NA
NA
NA
NA
NA
NA
ŋs cool
12/7°C
%
227 230 229
NA
NA
NA
NA
NA
NA
NA
SEPR
12/7°C
Process high temp.
kWh/kWh
6,45
6,49
6,35
NA
NA
NA
NA
NA
NA
NA
Integrated Part Load Value
IPLV.SI
kW/kW
6,491 6,657 6,658 6,051 6,301 6,425 6,306 6,052 6,332 6,180
Sound levels - standard unit
Sound power level
(1)
dB(A)
95
95
95
99
99
99
99
102
102
102
Sound pressure level at 1 m
(2)
dB(A)
78
78
78
82
82
82
82
84
84
84
Sound levels - standard unit + low noise level option
Sound power level
(1)
dB(A)
-
-
-
96
96
96
96
100
100
100
Sound pressure level at 1 m
(2)
dB(A)
-
-
-
78
78
78
78
82
82
82
Dimensions
Length
mm
2724 2724 2724 2741 2741 2741 2741 3059 3059 3059
Width
mm
928
928
928
936
936
936
936
1090 1090 1090
Height
mm
1567 1567 1567 1692 1692 1692 1692 1858 1858 1858
Operating weight
(3)
kg
2017 2036 2072 2575 2575 2613 2644 3407 3438 3462
Compressors
Semi-hermetic screw compressors, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
1
Refrigerant
(3)
R-134a
Circuit A
kg
84
80
78
82
82
82
82
145
135
125
teqCO
2
120
114
112
117
117
117
117
207
193
179
Summary of Contents for HYDROCIAT LW HE Series