No.
PARAMETER NAME
PARAMETER ADJUSTMENT
Notes
Description
Display conditions
Adjustment
possible
By default
Adjustment
conditions
A178
HYST. STAGE 4 COIL 2
A02 = 2 and A05 = 1 and
A08 ≥ 4
1 to 10°C
(increments of 1)
5
If A05 = 1 or 2
water circuit
On/Off control ONLY
with CONDENSER and
DRYCOOLER before
version V07
HYST. STAGE 4 COIL.2 CIR.1
A02 = 2 and A05 = 2 and
A08 ≥ 4
2 to 6 bar (0.5
increments)
3.5
If A05 = 1 or 2
refrig. circuit
A179
STAGE 5 COIL 2
DIFFERENCE
A02 = 2 and A05 = 1 and
A08 ≥ 5
1 to 5°C (in increments
of 1)
2
If A05 = 1 or 2
water circuit
A180
HYST. STAGE 5 CIRCUIT 2
A02 = 2 and A05 = 1 and
A08 ≥ 5
1 to 10°C
(increments of 0.5)
5
If A05 = 1 or 2
water circuit
HYST. STAGE 5 COIL.2 CIR.1
A02 = 2 and A05 = 2 and
A08 ≥ 5
2 to 6 bar (0.5
increments)
3.5
If A05 = 1 or 2
water circuits
A181
STAGE 6 CIRCUIT 2
DIFFERENCE
A02 = 2 and A05 = 1 and
A08 ≥ 6
1 to 5°C (in increments
of 1)
2
If A05 = 1 or 2
water circuit
STAGE 6 COIL.2 CIR.1
DIFFERENCE
A02 = 2 and A05 = 2 and
A08 ≥ 6
0.5 to 3 bar
(increments of 0.5)
0.5
If A05 = 1 or 2
refrig. circuit
A182
HYST. STAGE 6 COIL 2
A02 = 2 and A05 = 1 and
A08 ≥ 6
1 to 10°C
(increments of 0.5)
5
If A05 = 1 or 2
water circuits
HYST. STAGE 6 COIL.2 CIR.1
A02 = 2 and A05 = 2 and
A08 ≥ 6
2 to 6 bar (0.5
increments)
3.5
If A05 = 1 or 2
refrig. circuit
A182.1
STAGE 7 COIL 2
DIFFERENCE
A02 = 1 and A03 = 1 and
A08 ≥ 7
1 to 10°C
(increments of 0.5)
5
If A03 = 1 or 2
water circuit
A182.2
HYST. STAGE 7 COIL 2
A02 = 1 and A03 = 1 and
A08 ≥ 7
1 to 10°C
(increments of 0.5)
5
If A03 = 1 or 2
water circuit
A183
HYST. STAGE 1 COIL.2 CIR.2
A02 = 2 and A05 = 2
1 to 20°C
(increments of 0.5)
5
If A05 = 2
water circuits
2 to 6 bar (0.5
increments)
3.5
If A05 = 2
refrig. circuit
A184
STAGE 2 COIL.2 CIR.2
DIFFERENCE
A02 = 2 and A05 = 2 and
A08 ≥ 2
1 to 5°C (in increments
of 1)
2
If A05 = 2
water circuits
0.5 to 3 bar
(increments of 0.5)
0.5
If A05 = 2
refrig. circuit
A185
HYST. STAGE 2 COIL.2 CIR.2
A02 = 2 and A05 = 2 and
A08 ≥ 2
1 to 10°C
(increments of 1)
5
If A03 = 2
water circuit
2 to 6 bar (0.5
increments)
3.5
If A05 = 2
refrig. circuit
A186
STAGE 3 COIL.2 CIR.2
DIFFERENCE
A02 = 2 and A05 = 2 and
A08 ≥ 3
1 to 5°C (in increments
of 1)
2
If A03 = 2
water circuit
0.5 to 3 bar
(increments of 0.5)
0.5
If A05 = 2
refrig. circuit
A187
HYST. STAGE 3 COIL.2 CIR.2
A02 = 2 and A05 = 2 and
A08 ≥ 3
1 to 10°C
(increments of 1)
5
If A05 = 2
water circuit
2 to 6 bar (0.5
increments)
3.5
If A05 = 2
refrig. circuit
A188
STAGE 4 COIL.2 CIR.2
DIFFERENCE
A02 = 2 and A05 = 2 and
A08 ≥ 4
1 to 5°C
(increments of 1)
2
If A05 = 2
water circuit
0.5 to 3 bar
(increments of 0.5)
0.5
If A05 = 2
refrig. circuit
A189
HYST. STAGE 4 COIL.2 CIR.2
A02 = 2 and A05 = 2 and
A08 ≥ 4
1 to 10°C
(increments of 0.5)
5
If A05 = 2
water circuit
2 to 6 bar (0.5
increments)
3.5
If A05 = 2
refrig. circuit
A190
STAGE 5 COIL.2 CIR.2
DIFFERENCE
A02 = 2 and A05 = 2 and
A08 ≥ 5
1 to 5°C (in increments
of 1)
2
If A05 = 2
water circuit
0.5 to 3 bar
(increments of 0.5)
0.5
If A05 = 2
refrig. circuit
A191
HYST. STAGE 5 COIL.2 CIR.2
A02 = 2 and A05 = 2 and
A08 ≥ 5
1 to 10°C (in
increments of 0.5)
2
If A05 = 2
water circuit
2 to 6 bar (0.5
increments)
3.5
If A05 = 2
refrig. circuit
A192
STAGE 6 COIL.2 CIR.2
DIFFERENCE
A02 = 2 and A05 = 2 and
A08 ≥ 6
1 to 5°C
(increments of 1)
2
If A05 = 2
water circuit
0.5 to 3 bar
(increments of 0.5)
0.5
If A05 = 2
refrig. circuit
A193
HYST. STAGE 6 COIL.2 CIR.2
A02 = 2 and A05 = 2 and
A08 ≥ 6
1 to 10°C (in
increments of 0.5)
5
If A05 = 2
water circuit
2 to 6 bar (0.5
increments)
3.5
If A05 = 2
refrig. circuit