![CIAT AeroCONNECT 1B Control Manual Download Page 33](http://html1.mh-extra.com/html/ciat/aeroconnect-1b/aeroconnect-1b_control-manual_2606704033.webp)
EN
EN - 31
EN7510364-00
Registers 578 and 579:
A113: Misting control voltage threshold
Register 580:
A129 Permanent fan fault
0
5 faults in 1 hour
1
After first fault
Register 581:
A109 Operation
0
Cooling
1
Warming without control
2
Warming with control
Register 582 and 583:
A109.1: Outdoor temperature warming operating order
Register 584 and 585:
A105 : Threshold mini of fan speed in mixed control 3
9.9 Function 1, 2: read N bits
9.9.1 Remote alarm and operating state
(1 = Fault)
Bit 1:
Fan fault, stage 1, line 1
Bit 2:
Fan fault, stage 2, line 1
Bit 3:
Fan fault, stage 3, line 1
Bit 4:
Fan fault, stage 4, line 1
Bit 5:
Fan fault, stage 5, line 1
Bit 6:
Fan fault, stage 6, line 1 or fan fault stage 7, line 1
Bit 7:
Fan fault, stage 1, line 2
Bit 8:
Fan fault, stage 2, line 2
Bit 9:
Fan fault, stage 3, line 2
Bit 10:
Fan fault, stage 4, line 2
Bit 11:
Fan fault, stage 5, line 2
Bit 12:
Fan fault, stage 6, line 2
Bit 13:
Pressure or temperature sensor fault, coil 1, circuit
(from V07)
Bit 14:
Temperature sensor or pressure fault, coil 1, circuit 2
Bit 15:
Temperature sensor or pressure fault, coil 2, circuit 1
Bit 16:
Temperature sensor or pressure fault, coil 2, circuit 2
Bit 17:
On/off (1 = on
on and AOC closed)
Bit 18:
Spray state 1 = on
Bit 19:
Free cooling state 1 = on
Bit 20:
General fault summary
Bit 21:
Connection fault with the Diris module
9.9.2 Remote control
Read and write
Bit 31:
On/off (0 = off, 1 = on)
Bit 32:
Setpoint 1/setpoint 2 control (0 = Setpoint 1, 1 = Setpoint 2)
9.9.3 Status of the fan outputs
Read-only
Bit 40:
Fan state, stage 1, line 1 (1 = on)
Bit 41:
Fan state, stage 2, line 1 (1 = on)
Bit 42:
Fan state, stage 3, line 1 (1 = on)
Bit 43:
Fan state, stage 4, line 1 (1 = on)
Bit 44:
Fan state, stage 5, line 1 (1 = on)
Bit 45:
Fan state, stage 6, line 1 (1 = on)
Bit 46:
Fan state, stage 1, line 2 (1 = on)
Bit 47:
Fan state, stage 2, line 2 (1 = on)
Bit 48:
Fan state, stage 3, line 2 (1 = on)
Bit 49:
Fan state, stage 4, line 2 (1 = on)
Bit 50:
Fan state, stage 5, line 2 (1 = on)
Bit 51:
Fan state, stage 6, line 2 (1 = on)
Bit 52:
Fan state, stage 7, line 1 (1 = on)
Bit 53:
Fan fault, stage 7, line 1
9.9.4 Remote diagnostic Function 8
Read-only
Sub-function 0A:
Reset counters (No reply)
Sub-function 0B:
Frame received without CRC errors
Sub-function 0C:
Frame received with CRC errors
Sub-function 0D:
Number of exception replies
Sub-function 0E:
Frames sent excluding broadcast
Sub-function 0F:
Broadcast request received
Sub-function 10:
N.U.
Sub-function 12:
Unprocessed character
9.9.5 Function 11 Event counters
Read-only