8.2 System start-up and configuration
●
Powering on the unit
:
The screen displays: "machine stopped on/off" in the
[2-Machine status]
menu
Press ESC to go back to the menu list.
●
Main parameters to be set
: select the
[5-Settings parameters]
menu.
For information on navigating, go to the "control console/navigation" section.
Parameter No.
Description
Default values
Display conditions
Menu 5: Settings parameters
A100
Language
EN
A103
Console control type
local
Before V07
A104
Communication mode (baud)
9600
CMS
A105
Bus number
1
CMS
From V07
A106
Beach without switching on the fan.
2
Control = On/Off
A107
Start time between stages.
120
Control = On/Off
A108
Time to stop between stages.
120
Control = On/Off
A110
Stage runtime balancing
yes
Control = On/Off (stages) or mixed
A113
Optimisation of water or electricity consumption
Water optimisation
Misting
From V07
A113.1
Misting control voltage threshold
10
M EC FMA
A114
Max. speed threshold
10
Control = Mixed or speed control
From V12
A115
Mini speed threshold EC fan
2
Mixed control 3
A116
Link with CIAT master chiller
yes
No longer visible from V09, see
parameter A316
Not available for
CIAT master
chillers
A120
No. of setpoints per circuit or coil
1
A121
Setpoint 1, circuit or coil 1
12 bar
A122
Setpoint 2, circuit or coil 1
12 bar
2 setpoints
or A123
A125
Setpoint 1, circuit 2
12 bar
2 refrig. ci flatbed unit
Setpoint 1, coil 2
V-type unit
or A124
A126
Setpoint 2, circuit 2
12 bar
2 setpoints & 2 refrig. circ.
+ flatbed unit
Setpoint 2, coil 2
2 set V-type unit
From V07
A129
Permanent fault
5 in 1
hour
A150
Stage 1 hysteresis, circuit or coil 1: 2 to 6 bar
3.5 bar
A151
Difference between stages 1 or 2, circuit or coil 1: from
0.5 to 3 bar
0.5 bar
Control = On/Off
+ no. of stages ≥ 2
A152 to A160-2
Hysteresis and difference of stages 2, 3, 4, 5, 6 or 7,
circuit or coil 1
3.5 bar
Control = On/Off
+ based on No. of stages
A161
Hysteresis stage 1 circuit 2:
from 2 to 6 bar
3.5 bar
2 refrig. ci flatbed unit
A162
Difference between stages 1 and 2 - circuit 2:
from 0.5 to 3 bar
0.5 bar
Control = On/Off
+ no. of stages ≥ 2
+ 2 refrig. ci flatbed unit
A163 to A171
Hysteresis and difference of stages 2, 3, 4, 5 or 6, circuit
2
3.5 bar
Control = On/Off + based on No. of
2 refrig. ci flatbed
unit
A172
Stage 1 hysteresis, coil 2: 2 to 6 bar
3.5 bar
V-type unit
A173
Difference between stages 1 and 2 - coil 2:
from 0.5 to 3 bar
0.5 bar
Control = On/Off + No. of stages ≥
2 + V-type
A174 to A182-2
Hysteresis and difference of stages 2, 3, 4, 5, 6 or 7 - coil
2
3.5 bar
Control = On/Off + based on No. of
V-type unit
A199
Outdoor misting temperature
35°C
Misting/elec. optimisation
A200
Misting stage difference
0.5 bar
Misting/water optimisation & 1 refrig.
circuit
Misting stage difference, circuit or coil 1
Misting/water optimisation & 2 refrig.
circuits
A201
Misting stage difference, circuit or coil 2
0.5 bar
Misting/water optimisation & 2
refrig. circuit
Commissioning the unit: Power button
To rapidly change the setpoint values:
go directly to the [1 - Setpoints] menu