EN - 20
7 - DRYCOOLER CONFIGURATION
7.1 Configurations
Application
: drycooler with one or two coils
7.2 System start-up and configuration
●
Powering on the unit
:
The screen displays: "machine stopped on/off" in the
[2-Machine status]
menu
Press ESC to go back to the menu list.
●
Main parameters to be set
:
Select the
[5-Settings parameters]
menu.
For information on navigating, go to the "control console/navigation" section.
Parameter No.
Description
Default values
Display conditions
Menu 5: Settings parameters
A100
Language
EN
A103
Console control type
local
A104
Communication mode (baud)
9600
CMS
A105
Bus number
1
CMS
From V07
A106
Range without fan activation
2
Control = On/Off
A107
Activation time between stages
120
Control = On/Off
A108
Deactivation time between stages
120
Control = On/Off
A109
Operation
Cooling
A109.1
Outdoor temperature warming operating
order
10
A110
Stage runtime balancing
yes
Control = On/Off (stages) or mixed
A111
Free cooling
no
V-type or 1-coil unit/flatbed unit
without misting
(Induced draught)
Coil 2
Coil 1
Coil 2
Coil 1
(Forced draught)
Flatbed unit
V-type unit