EN7510364-00
Parameter No.
Description
Default value
Display conditions
A112
Selection air temperature
If the temperature drops below that of value "5" the
parameter is deactivated. Press the button to
re-enable the parameter.
10
Free cooling
A113
Optimisation of water or electricity consumption
Water optimisation Misting
From V07
A113.1
Misting control voltage threshold
10
M EC FMA
A114
Max. speed threshold
10
Control = Mixed or speed control
From V12
A115
Mini speed threshold EC fan
2
Mixed control 3
A116
Link with CIAT chiller
yes
No longer visible from V09, see parameter
A316
From V03
A117
Minimum T difference to deactivate free cooling
2
Free cooling
A118
Maximum T difference to activate free cooling
4
Free cooling
From V07
A119.1
Type of coil 1 fluid
Water
A119.2
Type of coil 2 fluid
Water
A120
No. of setpoints per coil
1
A121
Setpoint 1
60
V-type or 1-coil unit/flatbed unit
Setpoint 1, coil 1
2 coils + flatbed unit
A122
Setpoint 2
50
2 set V-type or 1-coil unit/flatbed unit
Setpoint 2, coil 1
2 set 2 coils/flatbed unit
A125
Setpoint 1, coil 2
60°C
2 coils/flatbed unit
A126
Setpoint 2, coil 2
50°C
2 set 2 coils/flatbed unit
From V07
A129
Permanent fault
5 in 1 hour
More visible
from V07 during
On/Off
control
A150
Stage 1 hysteresis: 1 to 20°C
5°C
V-type or 1-coil unit/flatbed unit
Hysteresis stage 1 coil 1: 1 to 20°C
2 coils/flatbed unit
A151
Difference between stages 1 and 2: 1 to 5°C
2°C
Control = On/Off + No. of stages ≥ 2 +
V-type or 1-coil unit/flatbed unit
Difference between stages 1 and 2 - coil 1:
1 to 5°C
Control = On/Off + No. of stages ≥ 2 + 2
coils/flatbed unit
A152 to
A160-2
Hysteresis of stages 2, 3, 4, 5, 6 or 7:
from 1 to 10°C
Difference of stages 2, 3, 4, 5, 6 or 7:
1 to 5°C
5°C
Control = On/Off + based on No. of
V-type or 1-coil unit/flatbed unit
Hysteresis of stages 2, 3, 4, 5, 6 or 7
- coil 1: 1 from to 10°C
Difference of stages 2, 3, 4, 5, 6 or 7
- coil 1: from 1 to 5°C
Control = On/Off + based on No. of stages
+2 coils/flatbed unit
A172
Hysteresis stage 1 coil 2:
1 to 20°C
5°C
2 coils/flatbed unit
A173
Difference between stages 1 and 2 - coil 2:
1 to 5°C
2°C
Control = On/Off + No. of stages ≥ 2
+ 2 coils/flatbed unit
A174 to
A182-2
Hysteresis of stages 2, 3, 4, 5, 6 or 7
- coil 2: from 1 to 10°C
Difference of stages 2, 3, 4, 5, 6 or 7
- coil 2: from 1 to 5°C
Control = On/Off + based on No. of stages
+2 coils/flatbed unit
A199
Outdoor misting temperature
35°C
Misting/elec. optimisation
A200
Misting stage difference
2°C
Misting/water optimi V-type or 1-coil
unit/flatbed unit
Misting stage difference, coil 1
Misting/water optimi 2 coils/flatbed
unit
A202
Misting stage difference, coil 2
2°C
Misting/water optimi 2 coils/flatbed
unit
●
Commissioning the unit: Power button
To rapidly change the setpoint values:
go directly to the
[1 - Setpoints]
menu