9.7 Counters (read-only)
Registers 300 and 301
: Fan runtime, stage 1, line 1
Registers 302 and 303
: Fan runtime, stage 2, line 1
Registers 304 and 305
: Fan runtime, stage 3, line 1
Registers 306 and 307
: Fan runtime, stage 4, line 1
Registers 308 and 309
: Fan runtime, stage 5, line 1
Registers 310 and 311
: Fan runtime, stage 6, line 1
Registers 312 and 313
: Fan runtime, stage 1, line 2
Registers 314 and 315
: Fan runtime, stage 2, line 2
Registers 316 and 317
: Fan runtime, stage 3, line 2
Registers 318 and 319
: Fan runtime, stage 4, line 2
Registers 320 and 321
: Fan runtime, stage 5, line 2
Registers 322 and 323
: Fan runtime, stage 6, line 2
Registers 324 to 398
: Spare
9.8 Remote configuration register (read and write)
Register 399:
Unit type (A01) 0
flat type, 1
V type
Register 400:
If A01 = type V: A02 parallel coil 0 = NO, 1 = YES
If A01 = flat
A02 number of coils
Register 401:
Coil 1 type (A03)
0
1 low-temperature water circuit
1
2 low-temperature water circuits
2
1 high-temperature water circuit
3
2 high-temperature water circuits
4
1 refrigerant circuit
5
2 refrigerant circuits
Register 402:
A04: Circuit type, coil 1
0
balanced circuit
1
unbalanced circuit
Register 403:
A05: Coil 2 type
0
1 low-temperature water circuit
1
2 low-temperature water circuits
2
1 high-temperature water circuit
3
2 high-temperature water circuits
4
1 refrigerant circuit
5
2 refrigerant circuits
Register 404:
A06: Circuit type, coil 2
0
Balanced circuit
1
Unbalanced circuit
Register 405:
A07: Control type
0
On/Off
1
Variable speed control
2
Mixed energy
Register 406:
A08: Number of fan stages
Register 407:
A09 :Number of fan lines
Register 408:
A10: Misting (0 = NO, 1 = YES)
Registers 409 and 410:
A30: HP sensor high value coil 1 circuit 1
Registers 411 and 412:
A31: HP sensor low value coil 1 circuit 1
Registers 413 and 414:
A32: HP sensor high value coil 1 circuit 2
Registers 415 and 416:
A33: HP sensor low value coil 1 circuit 2
Registers 417 and 418:
A34: HP sensor high value coil 2 circuit 1
Registers 419 and 420:
A35: HP sensor low value coil 2 circuit 1
Registers 421 and 422:
A36: HP sensor high value coil 2 circuit 2
Registers 423 and 424:
A37: HP sensor low value coil 2 circuit 2
Register 425:
A99: Locking
0
: NO
1
: YES
Register 426:
A15.1 Presence of energy management module
0
NO
1
YES
Register 427:
A15.2 Type of network
0
1BL - 1
2BL - 2
3BL - 3
3NBL
4
4BL - 5
4NBL
Register 428:
A16 Primary current transformer rating
Register 450:
A110: Optimised fan operation
0
NO
1
YES
Register 451:
A120: Number of setpoints
0
1 setpoint
1
2 setpoints via CMS system or console
2
2 setpoints per On/Off input