![CIAT AeroCONNECT 1B Control Manual Download Page 20](http://html1.mh-extra.com/html/ciat/aeroconnect-1b/aeroconnect-1b_control-manual_2606704020.webp)
EN7510364-00
EN - 18
6.2.2 Relay motherboard
To be installed by the customer in its main electrical cabinet
160
25
15
6
203.4
16
4
Ø 4.5
J2
J3
J1
J14
J15
J4
J12
J13
J6
J8
J2
J3
J1
J15
J4
J13
J6
J8
J5
J7
J11
J9
J5
J7
J11
J9
C
J10
A
J10
B
J14
J12
CONNECTOR/TERMINALS
DESIGNATION
DIRECTION OF ACTION
On/Off inputs
J6 terminals 1-3
Fan manual override
The fans turn on when the contact closes
J6 terms. 2-3
Automatic operation control
The machine stops when the contact opens
J6 terminals 4-6
Setpoint 1/Setpoint 2 selection
Setpoint 2 is enabled when the contact is closed.
Analogue Inputs
J7 terminals 1-2
Outdoor temperature sensor
J9 terminals 1-2-3
BUS feed connection to J10 of the water chiller board
J10 terminals 1-2-3
BUS power supply connected by shielded cable to J1 on relay board or J1 on remote control console. (terminal 1
to terminal 1, terminal 2 to terminal 2 and shielding to terminals 3).
J11 terminals 1-2-3
BUS power supply connected by shielded cable to J9 on the CONNECT2 board or J12 on the CONNECT
board or JA11 on the XTRACONNECT board. (terminal 1 to terminal 1, terminal 2 to terminal 2 and shielding to
terminals 3) or customer CMS.
Its potential-free (dry) contacts allow the following information to be viewed remotely:
CONNECTOR/TERMINALS
DESIGNATION
DIRECTION OF ACTION
J11 terminals 1-2-3
BUS feed connected by shielded cable to the unit's control board. (Terminal 1 to terminal 1, terminal 2 to terminal
2 and shielding to terminals 3).
J4 terminals 1-2-3
Single-phase 230 V power supply. (L - N T)
Terminal 1 Neutral
Terminal 2 Phase
Terminal 3 Earth
J13 terminals 1-2-3
If ADD3 board, terminal J1 connected to ADD3 board (30 cm of cable supplied with the ADD3 board)
J3 terminals 1-2
Unit running
The contacts are closed when the unit is running
without any faults.
J3 terminals 1-3
Sensor fault, coil 1, circuit 1
J3 terminals 4-5
Sensor fault, coil 2, circuit 1
J3 terminals 4-6
Fan fault, stage 1/fan
fault, stage 1, line 1
J3 terminals 4-7
Fan fault, stage 2/fan
fault stage 2, line 1
J3 terminals 4-8
Fan fault, stage 3/fan
fault stage 3, line 1
J3 terminals 9-10
Fan fault, stage 4/fan
fault stage 4, line 1
J3 terminals 11-13
Fan fault, stage 5/fan
fault stage 5, line 1
J3 terminals 14-15
Fan fault, stage 6/fan
fault stage 6, line 1
J3 terminals 14-16
Sensor fault, coil 1, circuit 2