Function parameter specific instruction
Control Function
F000 Operation Frequency Setting Range: 0.0 ~ Top Frequency Factory Setting: 5.0HZ
Function Instruction: Such settings are used to set the current operating frequency of the
Inverter. In the multi-spee d or program operation time, it is also
the setting source of the first sect speed frequency.
Note 1: When the frequency setting is controlled by panel key
, pressing
he
on the cont roll ing panel can adjust operating frequency directly.
Note 2 : Maximum of operation frequency is limited by Maximum Frequency (F004)
and frequency toplimit (F014).
F001 Choose operation control way Setting Range: 0~3 Factory Setting: 0
F001=0: Panel Control (positive rotating start,
F001=1:Outer terminal control(
F001=2:Outer terminal control (
F001=3:Outer terminal control (
Function Instruction: Such function is used to choose the controlling way of the start
and stop of Inverter.
Note 1: When choosing panel control (F001=0), outer terminal control has no use. Use
the keys on operation panel to control of the start and st op of
motor.
Note 2: When choosing panel control (F001=1), panel has no use.
Controlling terminal STF are connected with COM and RUN, STF a nd
COM are broken and stop, STR and COM are connected and reverse,
STR and COM are broken and stop.
Note 3: When choosing panel control (F001=2), panel has no use.
Controlling terminal STF and COM are connected and start, STF and COM
are broken and stop, STR and COM are conne cted and re verse, STR and COM
terminal are broken and RUN.
Note 4: When choosing panel control (F001=3), panel has no use.
X1~X4 multi-function terminals must have one terminal choosing outer NC
pushbutton. (Check Details in F093~F096 function choose), consist of
three-wire pushbutton control, otherwise this function has no use. Wiring
way see below picture :
Multi-Function
Terminal
F002 Frequency Setting Way Choice Setting Range: 0~4 Factory Setting: 0
F002=0: Frequency is set by key
on panel.
F002=1: Frequency is set by potentiometer on panel.
F002=2: Frequency is set by outer potentiometer or outer voltage DC 0~10V.
F002=3: Frequency is set by outer current DC 4~20mA.
F002=4: Frequency is set by out pushbutton up or down.
Function Ins truction: Such function is used to choose operating frequency (when
operating in multi-speed or by progr am, used a s the operating
frequency of one sector speed) settings or control source.
Note: When choosing frequency is set by oute r pushbutton up or down (F002=4),
X1~X4 multi-function terminals must have one choosing outer pushbutton
up, one choosing outer pushbutton down (details are in function code F093
~F096 functio n choice), other wise this function will be useless, seperatelly
connect chosen terminal with COM terminal
F003 Machine Stop way choice Setting Range: 0~3 Factory Setting: 0
F003=0: Deceleration and Stop
F003=1: Free Stop
F003=2: Immediate DC Stop
F003=3: Out Free Stop
Function Instruction: Such function is used to choose the stop way of the Inverter.
Note 1: When choosing deceleration and stop (F003=0), motor decelerate to DC
operation frequency F076, press F077 DC operation and F075 DC operation
time stop.
Note 2: When choosing free stop (F003=1), after Inverter received stop demand,
immediately cut off the power supply, motor freely stop.
Note 3: When choosing immediate DC stop (F003=2), after Inverter received stop
demand, immediately press F077 DC operation stop and F075 DC operation
time stop.
Note 4: When choos ing out free stop (F003=3), X1~X4 multi-function terminal must
have one termina l to choose out free stop (details are in function code F093
~F096 function choice), otherwise this function will be useless, connection
of chosen terminal and COM terminal can carry out out free stop.
Article6 Function parameter illustration