The factory default setting of the deceleration time for the inverter (>30KW) is 20.0S.
Basic Function
F011 Analog input corresponding with highest frequency Setting Range: 0~100%
Factory Setting: 100%
F012 Analog input corresponding with lowest frequency Setting Range: 0~100%
Factory Setting: 1%
Function Instruction: When F011 and F012 functions are used to set analog input, the
corresponding analog relation of the highest and lowest frequency.
Note: When F011>F012, the higher the analog input value is, the higher the rotating
speed will be. When F011<F012, the higher the analog input value is, the lower the
rotating speed will be.
Frequency
Voltage
Voltage
Frequency
Positive Character F011>F012
Reverse Character F011>F012
F013 Motor over-current protection current Setting Range: 50~110% Factory Setting:100%
Function In struction: Such function is used to protect the motor over-current and factory
set to be the rated current of the Inverter. When the power of the matched motor
is lower than the power of the Inverter, set this value according to the rate of the
actual used motor's rated current and the rated current of the Inverter. When the
Inverter is used to protect several motors, it can not be used to protect motor. Now
install thermal relay for each motor.
F014 Frequency Toplimit Setting Range: frequency lowlimit ~ 400HZ Factory Setting: 50.0HZ
F-15 Frequency Lowlimit Setting Range: 0.0HZ ~ frequency toplimit Factory Setting: 1.0HZ
Function Instruction: F014 and F015 function are used to set motor's highest output
and lowest output frequency of the acceptable Inverter. If operating frequency
setting is lower than the frequency toplimit or higher than the frequency toplimit, the
Inverter only can work in the setting range of the frequency lowlimi t and frequency
toplimit.
Note 1: Frequency toplimit, bottom value is limited by frequency lowlimit (F015).
Note 2: Frequency lowlimit top value is limited by frequency toplimit (F014).
Top Frequency
Frequency Toplimit
Frequency Lowlimit
Top Frequency
Frequency input sigal
F016 Start Frequency Setting Range: 0.0~10.0HZ Factory Setting: 1.0HZ
Function Instruction: Such function is used to set the start frequency of the Inverter.
Note: If this value is set too much, it is easily to occur jump fault.
F017 Start time-delay time Setting Range: 0.0~60.0S Factory Setting: 0.5S
Function Instruction: Such function is used to improve motor's start character, so as to
ensure motor can be fully started in the set time.
Frequency
Operating Frequency
Start Time-Delay Time
Time
F018 Acceleration Time Setting Range: 0.1~999.9S Factory Setting: 10.0S
Function Instruction: Such function is used to set the time of output frequency rises from
0 to the top frequency of the Inverter. In the operation of multi-speed or by program,
it is also the setting source of the acceleration time of the first sector.
Note: The factory setting of the Inverter deceleration time above 30KW is 20.0S
F019 Deceleration Time Setting Range: 0.1~999.9S Factory Setting: 10.0S
Function Instruction: Such function is used to set the time of output frequency fall from
top frequency of the Inverter to 0. In the operation of multi-speed or by program,
it is also the setting source of the deceleration time of the first sector.
F020 Choice of Acceleration, Deceleration Curve Method Setting Range: 0~1
Factory Setting: 0
F020=0: operation in beeline way.
F020=1: operation in S Curve way, based on the operating frequency.
Function In struction : Such function is used to choose Acceleration, Deceleration Curve
Method is in beeline way or S Curve way. When operating in S Acceleration,
Deceleration Curve, it has slowly acceleration and deceleration with no impact.
Frequency
Operation
Frequency
Acceleration Time
Deceleration Time
Operation in Beeline Way
Frequency
Operation
Frequency
Acceleration Time
Deceleration Time
Time
Time
Operation in S Curve Way
Article6 Function parameter illustration