                  Arbitrary V/F Curve 

for Fans and Pumps

          F005                                                

          F008                                                       

          F010                                                 

                  F009       F007

F004  

F004

F005

F007

F008

F009

F010

50.0Hz

380V

25.0 Hz

25%

0.0 Hz

5%

V/F Curve Setting

F004  Highest Frequency  Setting Range: Lowest Frequency~400.0HZ  Factory Setting:50.HZ

Funct ion In struc tion:  Such function is used to set the highest frequency of the Inverter's 
     allowed output. All input frequency setting signal (0~5VDC,0~10V,4~20mA) top value 
     correspond to this frequency range.

F005  Highest Voltage      Setting Range: (380V) 320~480V     Factory Setting: 380V

Function Instruction: Such function is used to set the highest output voltage of the tran
     sducer.
Note: This value must be or less than the rated voltage of the motor, and is normally 
     set to be the rated voltage of the motor.

F006   Rated Frequency of Motor   Setting Range: Middle Frequency~400.0HZ       
Factory Setting: 50.0HZ

Function Instruction: Such function is used to set the rated frequency of motor.

F007    Midd le Frequency     Setti ng Range: Lowest Frequency ~ Highest Frequency  
Factory Setting: 25.0HZ

Function Instruction: Such function is used to set the random middle frequency value of 
     V/F curve.

Note: Middle frequency top value is limited by the highest frequency (F004), bottom 
value is limited by the lowest frequency (F009).

F008    Middle Voltage      Setting Range: Lowest Voltage ~ 99% Rated Voltage    
Factory Setting: 50%

Function Instruction: Such function is used to set the random middle voltage value of 
    V/F curve.
Note: Middle voltage top value is limited by the highest voltage (F005), bottom value is 
    limited by the lowest voltage (F010).

F009    Lowest Frequency   Setting Range: 0.0~10.0HZ    Factory Settings: 0.0HZ

Function Instruction: Such function is used to set the lowest output frequency of the 
     Inverter.

F010   Lowest Voltage   Setting Range: 0 ~ 10% Rated Voltage    Fa ctory Settings: 1%

Function Instruction: Such function is used to set the lowest output voltage of the 
    Inverter. 

  Below are V/F Curve Type

  Generally Used V/F Curve Setting Value

Voltage

Frequency

   

Normal V/F Curve Settings

Function Code Parameter Value

High Starting Torque 

    V/F Curve Setting Value

Voltage

Voltage

Frequency

Frequency

Function Code Parameter Value

Function Code Parameter Value

Fan, Bump etc. V/F Curve 

    Setting Value

Article6    Function parameter illustration

Article6    Function parameter illustration

                  Arbitrary V/F Curve 

for Fans and Pumps

                  Arbitrary V/F Curve 

High Starting Torque

Summary of Contents for ZVFG7 series

Page 1: ...ZVFG7 SERIES ZVFP7 SERIES INVERTER USER S MANUAL INVERTER...

Page 2: ...ble shooting and etc of inverters Ensure that this manual is made available to the final user and keep it handy for future reference If there is any doubt or question please contact the Technical Serv...

Page 3: ...4 3 The content of dispay 27 Article 5 Run in test 28 5 1 Run in test 29 5 2 Operation of run 30 Article 6 Reference on Function Data 31 6 1The fleet of function data 32 6 2Detail reference of functi...

Page 4: ...ment failure Do not touch any active componentsin the inverter for high voltage remains in it when the indicator light isON after the power cut Cautions for Installation and connection The installatio...

Page 5: ...rrotate Do not modify the set parametervalue for inverter if there isno special requirement for the factory default settinghas been done properly Otherwise it may cause damage to the inverter or equip...

Page 6: ...ease open the carton and check it as soon as you got the products Checking item 1 check the Inverter destroied or not 2 Packing box concluding a piece of Inverter a brochure 3 Check the name plate be...

Page 7: ...ing output 250V 2A contact open electric pole output Other function Diagram run PID restart after transient stop restart after accident frequency down up data locking crawl function absorbing function...

Page 8: ...he sunshine without dust without combustible and corrosion gas No granule of metal or foam ofmetal place No shake no electro magnetic interference place 3 1 2 Caution of installation The board must be...

Page 9: ...U V W otherwise it will destroy the Inverter Dangerous It is forbidden to connect the wire when the Inverter is in use Be sure to operate it when cut off the power after five minutes The terminal blo...

Page 10: ...S T connectfreely Output terminal U V W connect the three phrase motor if you find the rotating reverse please adjust the two phrase arbitrary The Inverte r below 15KW concluding the brake unit if yo...

Page 11: ...terminal Positive rotata stop Reverse stop Accident exterior Accident reset Multi speed 1 Multi speed 2 Multi speed 3 Crowl function Positive rotate after connecting COM break stop Reverse rotate afte...

Page 12: ...00A 400A 1 5 2 5 2 5 4 6 6 10 10 16 16 25 25 35 35 50 50 70 3 2 4Directory of complement electric Complement of circuit breaker magnetic starter and the width of wire with the Inverter Article 3 Insta...

Page 13: ...nel 1 Control panel 2 with potentIometer RLN STOP JOG FWD REV JOG PRGM REV FUNG DATA RUN STOP RESET JOG PRGM REV FUNG DATA RUN STOP RESET FWD REV JOG STOP LED display area Display current status run s...

Page 14: ...an choose the position of modify data Illustration of indicator Title of indicator Illustration Stop Positive Reverse Crawl After the Inverter connect the power and it is not start the indicator is li...

Page 15: ...tion Illustration Display F000 enter into the function setting Press four times display F004 Press one time 0 in the between is flashing Press one time display F014 Press one time the forward 0 is fla...

Page 16: ...he output voltage of the run Display the AC voltage of bus bar wire Display the present speed of the Inverter Display the feedback data when PID run Display the data setted when PID run Display the da...

Page 17: ...play reduce from P50 0 to P0 0 if everything is ok operate the next step Inverter stop to output motor stop rotate run in test finish Gernerally please repeat servral times from the first step to the...

Page 18: ...teriorTerminal control positive start stop reverse stop 2 ExteriorTerminal control positive start stop reverse positive 3 ExteriorTerminal control positive start reverse start stop Choice of frequency...

Page 19: ...ency F004 0 1 999 9S 0 1 999 9S Highest frequency F004 0 1 999 9S 0 1 999 9S Highest frequency F004 5 0Hz 10 0S 10 0S 10 0Hz 10 0S 10 0S 20 0Hz 10 0S 10 0S 30 0HZ 10 0S 10 0S 40 0HZ Multi speed run Fu...

Page 20: ...rting AC brake torque 0 0 25 0S 0 0 25 0HZ 0 30 0 3 s 3 0HZ 4 Counter funtion Function code Title function Range of setting Factory parameter Note Counter mode Counter parameter 0 Expiry 1 Mode of up...

Page 21: ...nction choice 0 Multi speed 1 1 Multi speed 2 2 Multi speed 3 3 Exterior lift button 4 Exterior fall button 5 Exterior crawl function 6 Normal close botton 7 Exterior stop free 8 counter 9 counetr to...

Page 22: ...nal F002 Frequency Setting Way Choice Setting Range 0 4 FactorySetting 0 F002 0 Frequency is set by key on panel F002 1 Frequency is set by potentiometer on panel F002 2 Frequency is set by outer pote...

Page 23: ...ncy Factory Setting 25 0HZ Function Instruction Such function isused to set therandom middle frequencyvalue of V F curve Note Middle frequency top value is limited by the highest frequency F004 bottom...

Page 24: ...owlimit F015 Note 2 Frequency lowlimit top value is limited by frequency toplimit F014 Top Frequency Frequency Toplimit Frequency Lowlimit Top Frequency Frequency input sigal F016 Start Frequency Sett...

Page 25: ...eleration Time Crawl Instruction Time Crawl Deceleration Time Multi Speed Operation In multi speed operation F000 is the operation frequency of the first sector F018 is the acceleration time ofthe fir...

Page 26: ...or 7 speed when the Inverter is operated in multi speed or by program Function Instruction These functions are used to set the frequency acceleration time deceleration time of the sector 8 speed when...

Page 27: ...aximum Target Value Setting Range 0 9999 Factory Setting 1000 Function Instruction Such function is used to set the maximumtarget value when PID is operated F068 Relevant Feedback Value of Maximum Tar...

Page 28: ...everse Carrier Wave Frequency abridged general view is as below Carrier Wave Frequency Electromagnetism Noise Disturbance Leakage Current Fever Value Large Small Small Large Small Large Note Carrier w...

Page 29: ...ut is analogue signal input ratio of the maxim um output freque ncy value with relevant frequency set signal value is frequency gain in another word when input signal is not more than 10V 20mA throug...

Page 30: ...put frequency and continue recovery to operation frequency after voltage restored to be normal F102 Acceleration Over current Stall prevention Function Setting Setting Range 80 180 Factory Setting 130...

Page 31: ...ruction After fault Inverter will restore operation totally 10 times are allowed to restore operation after fault of every power on F112 Fault Restart Wait Time Setting Range 0 60S Factory Setting 10S...

Page 32: ...connected terminal phases Load change suddenly Accelerate time too short Motor jammed turn Inverter inner malfunction Input voltage abnormal Decelerate time to short Unsuitable braking component Load...

Page 33: ...Yes No Yes No Yes No 7 2 2 Over voltage over voltage when accelerating when decelerate when constant speed over voltage over voltage OU 1 Decrease the power voltage to be within the bound of regulate...

Page 34: ...stic Change to use out connected thermal relay Whether the over current setting is suitable Rectify the setting value Whether the on load is too big Maybe because of mal function or mal operating Plea...

Page 35: ...unction Yes No No Yes Yes Yes No No Yes No Yes Yes No No Yes Yes No No Yes Yes No No Yes Yes No No No Yes No Yes No Yes Yes No No Yes 7 3 2 Motor could operate but couldn t change speed Motor could op...

Page 36: ...hip on the circuit board Attention please don t leave tool and other eyewinker inthe Inverter or else it ll bring malfunction Attention please close the cover and screwedtightly after the examination...

Page 37: ...it board Other device 2 3 years 4 5years 5 8years According to the examination conditions Transportation and Deposit 8 2 1 transportation of Inverter put the Inverter upward when transport it acutely...

Page 38: ...0T 4150T 300 180 280 130 168 7 d A B W Outline dimension and installation dimension Article9 Outline dimension and installation dimension Article9 Outline dimension and installation dimension Type Pow...

Page 39: ...g to this using handbook or problem induced by repair and rebuildpersonally without permission Problem induced by using beyond the standard requirement Damage induced by move or storage afterpurchasin...

Page 40: ...rating panel out press downward the arrow directs emphatically by hand then pull out the operating panel 2 Install the leading out panel on the Inverter 3 Put the pulled out operating pane l in the in...

Page 41: ...the Inverter then the Inverter could be repaired and maintained conveniently Please don t use it as the daily on and off switch for the Inverter Magnetic contactor It s unnecessary to install magneti...

Reviews: