Installation
9
Chloride Linear Plus Series Rack-mount UPS User Instruction Manual
inearP
Cable Sizes and
Current
The following table indicates the recommended sizes of conductors in accordance with the NEC
®
. (Air
temperature surrounding the conduits not greater than 86°F (30°C).)
NOTE: Cable sizes are suggested and based on standard configurations. Installers should verify correct
conductor sizes pursuant to NEC
®
and/or state or local codes. If the installation requires long conductor
runs, consult NEC
®
and/or state or local codes to account for electrical losses.
WARNING: Particularly sensitive equipment may be susceptible to interference, in order to prevent this
it is suggested that input, output and any external battery cables to the UPS be housed in earthed, metal
conduits or that shielded cables be used. Routing of cables (e.g. power supplies, communication or data
Table 5. Mechanical data Linear Plus Rack-mount 6 kVA/10 kVA
UPS-TYPE
Linear Plus
Rack-mount 6 kVA
Linear Plus
Rack-mount 10 kVA
Mechanical Data
UPS
Net Weight - lbs (kg)
53 (24)
57 (26)
Unit dimensions
Width
19 (482.6)
Height
5.1 (130)
Depth
26 (660)
28.1 (715)
Body dimensions
Dimensions - in (mm)
Width
16.1 (410)
Height
5.25 (130) (3 U)
Depth
26 (660)
Battery
extensions
Type
LPBP100-2
Weight - lbs (kg)
152 (69)
Battery
dimensions
Dimensions - in (mm)
Width
(16.1) 410
Height
5.25 (130) (3 U)
Depth
26 (660)
26 (660)
Table 6. Cable Sizes
Term ID
Description
6 kVA
10 kVA
main wire
gauge
(awg
term
torque
(in-lbs)
min wire
temp
(°C)
*
main
wire
gauge
(awg
term
torque
(in-lbs)
min wire
temp (°C)*
MAIN
L/N
Line 1 (Main)
8
40
75
6
45
75
L
Line 2 (Main)
8
40
75
6
45
75
Chassis Ground
**
40
75
**
45
75
OUTPUT
L/N
Output Term 1
10
35
75
6
45
75
L
Output Term 2
10
35
75
6
45
75
Output Term 3
10
35
75
6
45
75
* Use insulated copper wire rated 75°C minimum.
** Must be no smaller than wire connected to mains L and L/N.
NOTE: For installation per IEC regulations: If installing units per regulations IEC-287 and DIN VDE 0298, 6 kVA model
should be wired (inputs and outputs) with 6 mm
2
cable torqued to 4.5 nt-m; and 10kVA model (inputs and outputs) should
be wired with 10 mm
2
cable torqued to 5.0 nt-m. (Based on 70°C cable and ambient of 30°C)