Operating the Device
Chloride Linear Plus Series Rack-mount UPS User Instruction Manual
16
Indication and
Operating Elements
Control Panel for the Linear Plus Rack-mount
The
OVERLOAD
indicator, red, (1) illuminates if the UPS is overloaded.
The
LOAD
LED strip (2) displays the load status of the UPS. See Table 8 on page 17 for details.
The
BYPASS
indicator, yellow, (3) illuminates when the UPS delivers voltage supplied from the mains
supply via the bypass.
The
INVERTER
indicator, green, (4) illuminates when the inverter is running.
The
BATTERY
LED chain, green, (5) indicates the charging state of the battery (normal operation). See
Table 9 on page 17 for details.
The
MAINS
indicator, green, (6) illuminates when normal mains voltage is present at the UPS input.
The
ALARM
indicator, red, (7) illuminates to indicate a UPS fault. An acoustical warning signal is
activated simultaneously; this signal is reset when the UPS is switched off.
The
button switches the inverter Off and the bypass On.
The
button switches the inverter On (bypass Off).
The inverter is activated by pressing the
button. Following a delay time of approximately 5 seconds,
the
BYPASS
indicator extinguishes and the
INVERTER
indicator illuminates.
Pressing the
button, blocks the inverter and switches the system to bypass.
UPS output voltage is
present.
Fig. 8: Symbols on the control panel of the UPS Linear Plus Rack-mount
The UPS indicates, by acoustic (buzz) and optical (LED) alarms, that a mains failure has occurred and is
still present. Different procedures, described below, may be followed to interrupt work in case of a
persistent mains failure.
Which of the procedures is applied depends, primarily, on the time required to close the program safely
and - if necessary - for an organized shut down of the operating system.
For example, work on a PC, which is individually supplied by the UPS, may be continued until the battery
nears minimum charge level. The buzzer indicates the mains failure periodically (every 4 seconds) and,
when minimum charge level is neared, once a second. This procedure is not often adopted. Although
battery recharge starts immediately when the mains is re-established, it can take several hours to recharge
the battery fully.
1
2
3
4
5
6
7
!
LOAD
BYPASS
INVERTER
BATTERY
MAINS
ALARM