Do not lay tools or metal parts on top of batteries
•
Disconnect charging source prior to connecting or disconnecting battery terminals
•
Determine if the battery in inadvertently grounded. If inadvertently grounded, remove source from
the ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock can be reduced if such grounds are removed during installation and
maintenance (applicable to equipment and remote battery supplies not having a grounded supply
circuit).
Storage
For extended storage at ambient temperature <77
°
F
(
< 25°C) the batteries should be charged for 5 hours
once every 4 months, at higher storage temperatures it is advised that this period be reduced to 2 months.
1. Connect the UPS (with attached external battery cabinets) to a mains outlet socket having an earth
connection or install fixed connections (in accordance with chapter “Installation” on page 7) to an
appropriate source.
2. Switch on the input miniature circuit breaker at the rear of the devices (UPS and external battery
cabinet) in the case of fixed connections.
3. After 5 hours, unplug from the mains supply or switch off the input miniature circuit breaker of the
UPS in case of fixed connections, and switch off the circuit breaker of the external battery cabinet.
4. Remove the UPS and external battery cabinet connections in the opposite sequence to that described
in “Installation”.
5. Note the date recharging was carried out on the packaging of the external battery cabinet.
Cleaning
NOTE: Do not use scouring powder or plastic-dissolving solutions to clean the UPS.
1. Switch off the UPS by pressing the OFF button following the shutdown procedure and disconnect
from the mains supply.
2. Make sure that the air vents on the UPS are not obstructed.
3. Remove dust from the air vents with a vacuum cleaner.
4. Clean the outside of the UPS housing by wiping with a dry or a slightly damp cloth.
NOTE: Do not allow liquid to get inside the UPS.
Interfaces
The Linear Plus Rack-mount is equipped with a serial interface COM 3 and an interface slot COM.
These interfaces can be used for:
• Direct communication between UPS and a workstation/server
• Integration of the UPS as client into a network with centralized monitoring via a ManageUPS
NET
II
SNMP adapter to put in slot COM
• Transfer of operational states to external alarm systems via voltage-free contacts: with interface card
SIC to put slot COM
The necessary communication software packages and interface cables are available as options.
Serial Interface COM 3
The 9-pole SUB-D connector (pin contacts) contains RS 232 compatible signals.