59
HVRT trigger voltage (%)
115.0
135.0
110.0
Power recovery step size (kW/s)
250.00
327.67
0
Active derating control
Default
Max
Min
Active derating (%)
110.0
110.0
0.0
Active step size (kW/s)
100.00
327.67
0.00
Overfrequency derating setting
0
1
0
Overfrequency derating trigger frequency
50.2
55.00
50.00
Overfrequency derating slope (%/Hz)
40.0
100.0
0.0
Overfrequency derating exit frequency (Hz)
50.06
55.00
50.00
Reactive power control (I)
Default
Max
Min
Reactive mode
0
6
0
Reactive Q setting
0.0
60.0
-60.0
PF setting
1.00
1.00
-1.00
PF (P) curve P1 (%)
10.0
110.0
0.0
PF (P) curve PF1
1.00
1.00
-1.00
PF (P) curve P2 (%)
100.0
110.0
0.0
PF (P) curve PF2
-0.9
1.00
-1.00
PF (P) curve trigger voltage (%)
90.0
110.0
80.0
PF (P) curve revocation voltage (%)
80.0
110.0
0.0
SVG control
0
1
0
SVG reactive power (%)
0.0
60
-60
Reactive power control (II)
Default
Max
Min
QU curve U1 (%)
108.0
110.0
100.0
QU curve Q1 (%)
0.0
100.0
-100.0
QU curve U2 (%)
110.0
110.0
100.0
QU curve Q2 (%)
-50.0
100.0
-100.0
QU curve U1i (%)
92.0
100.0
90.0
QU curve Q1i (%)
0.0
100.0
-100.0
QU curve U2i (%)
90.0
100.0
90.0
QU curve Q2i (%)
50.0
100.0
-100.0
QU curve trigger power (%)
10.0
100.0
5.0
QU curve revocation power (%)
5.0
100.0
5.0
APF enabled
0
1
0
Reactive power control step size (kVA/s)
100.00
327.67
0
Other protection parameters
Default
Max
Min
Upper limit of leakage current (mA)
5000
8000
0
DCI upper limit (mA)
1519
3038
0
DCI bias upper limit
500
682
0
Inverter current bias upper limit
60
256
0