INST.No.INE-454-P2 Software
Ver.1.2
-31-
7.2 Parameter programming/selection (engineering mode)
Parameter item
Sub display Parameter
Default
Chapter
Analog output scaling OutL
or
OutH
OutL
: Minimum value (0 to 6280ºC)
OutH
: Maximum value (0 to 6280ºC)
Minimum and
maximum value of
measuring range
4.1
Analog dummy output OutC
0
to
100
% 0%
4.2
Hold function
HoLd
no
: Hold function disable
PEAk
: Peak hold
SAMP
: Sample hold
no 4.3.1
Peak hold reset type H.rSt
no
: Reset disable
in
: Internal - time reset
Et
:External -remote contact reset
no
4.3.2
Peak hold reset time r.tiM
0.0
to
99.9
seconds
0.0 second
4.3.3
Measurement unit
unit
C
,
F
C
4.4
F i x e d n u m b e r
programming
tAu.d
Decimal point selection
2
4.5
Contact output
dout
no
: No contact output
ALM
: High/low temperature alarm
Err
: Self-diagnostic abnormal
ALM
4.6
Automatic emissivity
calculation
E.Aut no
: Calculation disable
in
: Internal - Key
Et
: External – Analog input
no 4.7
Measuring wevelength
selection
dEtc
2col,1col,2c2,2c1,InG2,InG1,Si(Refer to
Measurment wavelength table)
2col 4.8
Zero/span
adjustments
CAL
no
: Not execution
yES
: Execution
4.9
Zero/span
adjustments (1)
ZEro
SPAn
0
to
6280
ºC Minimum
and
maximum value of
measuring range
4.9.1
Zero/span
adjustments (2)
ZEro
SPAn
0
to
6280
ºC
Minimum and
maximum value of
measuring range
4.9.2
Correction after the
zero/span
adjustments.
(measured value
became abnormal)
CAL no
: Not execution
yES
: Execution
4.9.3-1)
Zero side data
display/setting by
IR-CA series
MES.Z
4.9.3-2)
Zero side data
display/setting by
furnace
temperature by a
reference radiation
thermometer
SEt.Z
4.9.3-3)
Span side data
display/setting by
IR-CA series
radiation
thermometer
MES.S
4.9.3-4)
7. Parameter programming/selection