R410A50Hz Universal Outdoor Series Technical Manual Floor & Ceiling Indoor Unit
95
GD Chigo Heating & Ventilation Equipment Co., Ltd.
2.Specifications
Model
CUA-18HR1
CUA-24HR1
CUA-36HR1
Indoor power supply
V/Ph/Hz
220~240/1/50
220~240/1/50
220~240/1/50
Cooling
Capacity
Btu/h
18000
24000
36000
KW
5.3
7.1
10.5
Input
W
65
150
300
Rated current
A
0.3
0.68
1.36
EER
W/W
2.7
2.78
2.62
Heating
Capacity
Btu/h
19800
26400
39600
KW
5.8
7.8
11.6
Input
W
65
150
300
Rated current
A
0.3
0.68
1.36
COP
W/W
3.32
3.47
3.19
Indoor fan
motor
Model
YSK110-65LD-4P3H85
YSK110-75LD-4P2
YSK110-180LD-4P2
Input
W
65
150
300
Capacitor
μF
3
5
5
Speed(Hi/Med/Lo)
r/min
1350/1270/1180
980/880/780
1330/1080/910
Indoor coil
Number of rows
3
2
3
Tube pitch x row pitch
mm
25×21.65
25×21.65
25×21.65
Fin spacing
mm
2
1.4
1.7
Fin type
Hydrophilic
Hydrophilic
Hydrophilic
Tube outside dia. and
type
mm
Ф9.52
Ф9.52
Ф9.52
inner grooved
inner grooved
inner grooved
Coil size(W x H x D)
mm
610x250x64.95
982×250×43.3
982×250×64.95
Number of circuits
3
5
5
Indoor air flow(Hi/Med/Lo)
m
3
/h
790/670/540
1100/860/740
1700/1300/1100
Indoor noise level(Hi/Med/Lo)
dB(A)
43/40/37
44/41/38
45/42/39
Indoor unit
Dimension(W×H×D)
mm
880×635×203
1245×680×247
1245×680×247
Packing(W×H×D)
mm
970×725×301
1325×770×325
1325×770×325
Net/Gross weight
kg
30/32
35/41
37/43
Refrigerant type
R410A
R410A
R410A
Refrigerant piping
Liquid side/Gas
side
mm
Φ6.35/Φ12.7
Φ9.52/Φ15.88
Φ9.52/Φ19.05
Drainage pipe
mm
30
30
30
Connection
wiring
Power Supply
From indoor unit
From indoor unit
From indoor unit
Indoor power wiring
mm
2
2.5
1.0
1.0
Signal wiring
mm
2
1.5
0.75
0.75
Controller
Standard for remote controller(wired controller for option)
Operation temp
°C
16
~
32
16
~
32
16
~
32
Ambient temp
°C
-7
~
43
-7
~
43
-7
~
43
Application area
m
2
20-35
28-50
40-70
Stuffing Quantity
(
20'/40'/40'HQ
)
132/270/306
75/165/189
75/165/189
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 7.5m(horizontal)
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 7.5m(horizontal)
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.