6.3 CCA-24HR1
MODEL
CCA-24HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
28ºC
35ºC
43ºC
21ºC D
15ºC W
Total capacity kW
7.29
6.94
6.61
6.34
Sensitive capacity kW
5.4
5.34
5.26
5.32
Input kW.
2.19
2.38
2.52
2.58
24ºC D
17ºC W
Total capacity kW
7.51
7.16
6.79
6.37
Sensitive capacity kW
5.62
5.55
5.51
5.35
Input kW.
2.34
2.53
2.61
2.72
27ºC D
19ºC W
Total capacity kW
7.66
7.29
7.10
6.62
Sensitive capacity kW
5.65
5.58
5.53
5.4
Input kW.
2.38
2.52
2.36
2.78
29ºC D
19ºC W
Total capacity kW
7.68
7.35
7.22
6.63
Sensitive capacity kW
6.45
6.24
6.21
6.05
Input kW.
2.42
2.58
2.69
2.79
32ºC D
23ºC W
Total capacity kW
7.78
7.54
7.36
6.83
Sensitive capacity kW
6.59
6.53
6.46
6.33
Input kW.
2.48
2.59
2.79
2.89
6.4 CCA-36HR1
MODEL
CCA-36HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
28ºC
35ºC
43ºC
21ºC D
15ºC W
Total capacity kW
10.81
10.25
9.75
9.33
Sensitive capacity kW
7.98
7.92
7.78
7.83
Input kW.
3.18
3.43
3.59
3.68
24ºC D
17ºC W
Total capacity kW
11.11
10.59
10.04
9.47
Sensitive capacity kW
8.32
8.23
8.15
7.96
Input kW.
3.34
3.58
3.73
3.92
27ºC D
19ºC W
Total capacity kW
11.31
10.81
10.50
9.75
Sensitive capacity kW
8.34
8.33
8.15
7.09
Input kW.
3.41
3.63
3.65
4.01
29ºC D
19ºC W
Total capacity kW
11.42
10.95
10.69
9.85
Sensitive capacity kW
9.58
9.26
9.22
8.94
Input kW.
3.39
3.69
3.83
4.08
32ºC D
23ºC W
Total capacity kW
11.52
11.11
10.95
10.02
Sensitive capacity kW
9.79
9.65
9.62
9.33
Input kW.
3.58
3.73
4.01
4.16