6.Capacity Tables
Cooling
6.1 CTA-18HR1
MODEL
CTA-18HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
45ºC
21ºC DB
15ºC WB
Total capacity kW
5.19
4.92
4.76
4.48
4.28
4.18
Sensitive capacity kW
4.12
3.93
3.81
3.56
3.41
3.31
Input kW.
1.15
1.29
1.47
1.61
1.8
1.96
24ºC DB
17ºC WB
Total capacity kW
5.67
5.39
5.27
4.91
4.71
4.58
Sensitive capacity kW
4.5
4.31
4.15
3.93
3.77
3.62
Input kW.
1.21
1.36
1.54
1.73
1.91
2.07
27ºC DB
19ºC WB
Total capacity kW
6.13
5.85
5.64
5.3
5.1
4.94
Sensitive capacity kW
4.82
4.68
4.5
4.13
4.09
3.96
Input kW.
1.25
1.48
1.62
1.79
2.01
2.18
32ºC DB
23ºC WB
Total capacity kW
7.1
6.73
6.5
6.15
5.9
5.72
Sensitive capacity kW
5.63
5.39
5.21
4.91
4.87
4.54
Input kW.
1.48
1.68
1.87
2.1
2.32
2.54
6.2 CTA-24HR1
MODEL
CTA-24HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
45ºC
21ºC DB
15ºC WB
Total capacity kW
6.87
6.54
6.32
5.94
5.75
5.53
Sensitive capacity kW
5.51
5.24
5.03
4.75
4.55
4.45
Input kW.
5.49
5.24
5.03
4.76
4.57
4.45
24ºC DB
17ºC WB
Total capacity kW
7.53
7.17
6.93
6.51
6.28
6.05
Sensitive capacity kW
6.02
5.76
5.52
5.22
5.03
4.84
Input kW.
1.67
1.90
2.16
2.36
2.61
2.86
27ºC DB
19ºC WB
Total capacity kW
8.18
7.80
7.52
7.11
6.84
6.61
Sensitive capacity kW
6.53
6.24
6.02
5.66
5.44
5.27
Input kW.
1.74
2.00
2.23
2.52
2.73
3.02
32ºC DB
23ºC WB
Total capacity kW
9.38
8.97
8.63
8.14
7.82
7.56
Sensitive capacity kW
7.53
7.17
6.921
6.51
6.25
6.04
Input kW.
2.02
2.32
2.61
2.87
3.16
3.44
6.3 CTB-18HR1
MODEL
CTB-18HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
45ºC
21ºC DB
15ºC WB
Total capacity kW
5.34
5.11
4.98
4.72
4.44
4.32
Sensitive capacity kW
4.33
4.19
3.98
3.73
3.55
3.41
Input kW.
1.30
1.49
1.57
1.65
1.92
2.18
24ºC DB
17ºC WB
Total capacity kW
5.92
5.54
5.47
5.17
4.95
4.88
Sensitive capacity kW
4.78
4.61
4.36
4.13
3.97
3.87
Input kW.
1.11
1.38
1.74
1.83
2.13
2.37
27ºC DB
19ºC WB
Total capacity kW
6.43
6.28
6.01
5.83
5.61
5.34
Sensitive capacity kW
5.03
4.78
4.54
4.13
3.98
3.76
Input kW.
1.20
1.58
1.73
1.90
2.21
2.48
32ºC DB
23ºC WB
Total capacity kW
7.3
6.93
6.71
6.45
6.15
5.92
Sensitive capacity kW
5.83
5.58
5.41
5.11
4.97
4.64
Input kW.
1.58