![Chigo CCA-18HR1 Technical Manual Download Page 21](http://html1.mh-extra.com/html/chigo/cca-18hr1/cca-18hr1_technical-manual_2601241021.webp)
R410A50Hz Universal Outdoor Series Technical Manual 4 -way Cassette Indoor Unit
18
GD Chigo Heating & Ventilation Equipment Co., Ltd.
6.5 CCA-48HR1
MODEL
CCA-48HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
28ºC
35ºC
43ºC
21ºC D
15ºC W
Total capacity kW
14.41
13.71
13.01
12.43
Sensitive capacity kW
10.65
10.54
10.39
10.45
Input kW.
4.14
4.48
4.7
4.83
24ºC D
17ºC W
Total capacity kW
14.83
14.12
13.43
12.58
Sensitive capacity kW
11.12
11.01
10.88
10.56
Input kW.
4.4
4.68
4.88
5.14
27ºC D
19ºC W
Total capacity kW
15.11
14.41
14
13.01
Sensitive capacity kW
11.17
11.09
10.9
10.65
Input kW.
4.48
4.73
5.00
5.24
29ºC D
19ºC W
Total capacity kW
15.24
14.54
14.26
13.15
Sensitive capacity kW
12.8
12.36
12.25
11.96
Input kW.
4.58
4.83
5.04
5.34
32ºC D
23ºC W
Total capacity kW
15.38
14.85
14.57
13.42
Sensitive capacity kW
13.07
12.9
12.82
12.48
Input kW.
4.69
4.91
5.23
5.44
6.6 CCA-48HR1
MODEL
CCA-60HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
28ºC
35ºC
43ºC
21ºC D
15ºC W
Total capacity kW
16.48
15.68
14.88
14.24
Sensitive capacity kW
12.16
12.07
11.91
11.97
Input kW.
4.75
5.14
5.37
5.54
24ºC D
17ºC W
Total capacity kW
16.96
16.16
15.36
14.40
Sensitive capacity kW
12.72
12.61
12.45
12.09
Input kW.
5.03
5.37
5.60
5.89
27ºC D
19ºC W
Total capacity kW
17.28
16.48
16.00
14.88
Sensitive capacity kW
12.79
12.69
12.48
12.21
Input kW.
5.14
5.43
5.81
6.00
29ºC D
19ºC W
Total capacity kW
17.44
16.64
16.32
15.04
Sensitive capacity kW
14.65
14.15
14.03
13.69
Input kW.
5.26
5.54
5.77
6.11
32ºC D
23ºC W
Total capacity kW
17.60
16.96
16.64
15.36
Sensitive capacity kW
14.96
14.75
14.64
14.29
Input kW.
5.37
5.60
6.00
6.23