![Chigo CCA-18HR1 Technical Manual Download Page 118](http://html1.mh-extra.com/html/chigo/cca-18hr1/cca-18hr1_technical-manual_2601241118.webp)
R410A50Hz Universal Outdoor Series Technical Manual Floor & Ceiling Indoor Unit
115
GD Chigo Heating & Ventilation Equipment Co., Ltd.
11.The Specification of Power
Type
CUA-18HR1
CUA-24HR1
CUA-36HR1
CUA-48HR1
CUA-60HR1
Power
Phase
1-phase
1-phase
1-phase
1-phase
1-phase
Frequency and Voltage
220-240V, 50Hz
Indoor Unit Power Wiring (mm
2
)
3×2.5mm
2
3×1.0mm
2
3×1.0mm
2
3×1.0mm
2
3×1.0mm
2
Indoor/Outdoor
Connecting
Wiring (mm
2
)
Ground Wiring
2.5mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
Strong Electric Signal
5×1.5mm
2
5×0.75mm
2
5×0.75mm
2
5×0.75mm
2
5×0.75mm
2