![Chigo CCA-18HR1 Technical Manual Download Page 61](http://html1.mh-extra.com/html/chigo/cca-18hr1/cca-18hr1_technical-manual_2601241061.webp)
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit
58
GD Chigo Heating & Ventilation Equipment Co., Ltd.
Heating
6.12 CTA-18HR1
MODEL
CTA-18HR1
HEATING
OUTDOOR CONDITIONS
Indoor Conditions
24ºC DB
18ºC WB
12ºC DB
11ºC WB
7ºC DB
6ºC WB
4ºC DB
3ºC WB
0ºC DB
-1ºC WB
-5ºC DB
-6ºC WB
-7ºC DB
-8ºC WB
15ºC
Capacity kW
10.15
8.14
6.75
6.11
5.69
5.08
4.75
Input kW.
3.15
2.48
2.07
1.93
1.87
1.8
1.68
18ºC
Capacity kW
9.56
7.68
6.36
5.75
5.4351
4.78
4.49
Input kW.
2.98
2.35
1.94
1.83
1.76
1.66
1.58
20ºC
Capacity kW
8.92
7.05
5.8
5.28
5.02
4.42
4.12
Input kW.
2.75
2.18
1.71
1.68
1.63
1.53
1.44
22ºC
Capacity kW
8.12
6.48
5.43
4.87
4.6
4.06
3.78
Input kW.
2.48
1.98
1.64
16
1.51
1.41
1.32
27ºC
Capacity kW
7.12
5.62
4.68
4.21
4.02
3.51
3.28
Input kW.
2.14
1.68
1.43
1.34
1.27
1.19
1.16
6.13 CTA-24HR1
MODEL
CTA-24HR1
HEATING
OUTDOOR CONDITIONS
Indoor Conditions
24ºC DB
18ºC WB
12ºC DB
11ºC WB
7ºC DB
6ºC WB
4ºC DB
3ºC WB
0ºC DB
-1ºC WB
-5ºC DB
-6ºC WB
-7ºC DB
-8ºC WB
15ºC
Capacity kW
13.78
11.02
9.18
8.26
7.79
6.85
6.42
Input kW.
4.30
3.43
2.87
2.71
2.55
2.46
2.30
18ºC
Capacity kW
12.92
10.34
8.63
7.74
7.31
6.45
6.00
Input kW.
4.05
3.18
2.67
2.54
2.41
2.30
2.13
20ºC
Capacity kW
12.00
9.56
8.01
7.14
6.77
6.03
5.60
Input kW.
3.75
3.00
2.50
2.35
2.23
2.14
2.00
22ºC
Capacity kW
11.04
8.76
7.32
6.60
6.22
5.48
5.11
Input kW.
3.42
2.71
2.28
2.14
2.01
1.88
1.82
27ºC
Capacity kW
9.54
7.60
6.37
5.73
5.40
4.72
4.43
Input kW.
3.00
2.33
2.00
1.91
1.75
1.68
1.60
6.14 CTB-18HR1
MODEL
CTB-18HR1
HEATING
OUTDOOR CONDITIONS
Indoor Conditions
24ºC DB
18ºC WB
12ºC DB
11ºC WB
7ºC DB
6ºC WB
4ºC DB
3ºC WB
0ºC DB
-1ºC WB
-5ºC DB
-6ºC WB
-7ºC DB
-8ºC WB
15ºC
Capacity kW
10.42
9.92
8.71
7.55
6.89
5.74
5.02
Input kW.
3.33
2.87
2.45
1.99
1.87
1.83
1.67
18ºC
Capacity kW
9.76
8.67
7.68
6.04
5.42
4.99
4.51
Input kW.
2.88
2.23
1.87
1.79
1.72
1.63
1.58
20ºC
Capacity kW
9.04
8.76
7.8
6.28
5.71
4.42
4.12
Input kW.
2.75
2.18
1.71
1.68
1.63
1.53
1.44
22ºC
Capacity kW
8.12
6.48
5.46
4.83
4.6
4.06
3.78
Input kW.
2.48
1.93
1.64
16.3
1.61
1.47
1.34
27ºC
Capacity kW
7.14
6.52
5.65
5.12
4.98
4.13
3.87
Input kW.
2.13
1.78
1.55
1.42
1.25
1.19
1.15
6.15 CTB-24HR1
MODEL
CTB-24HR1
HEATING
OUTDOOR CONDITIONS
Indoor Conditions
24ºC DB
18ºC WB
12ºC DB
11ºC WB
7ºC DB
6ºC WB
4ºC DB
3ºC WB
0ºC DB
-1ºC WB
-5ºC DB
-6ºC WB
-7ºC DB
-8ºC WB
15ºC
Capacity kW
13.68
10.96
9.12
8.21
7.79
6.58
6.4
Input kW.
4.18
3.4
2.76
2.65
2.53
2.4
2.27
18ºC
Capacity kW
12.84
10.2
8.52
7.1
7.31
6.38
6.01
Input kW.
4
3.12
2.61
2.5
2.4
2.23
2.09
20ºC
Capacity kW
11.5
9.45
7.8
7.08
6.59
5.92
5.48
Input kW.
3.6
2.88
2.28
2.2
2.03
2.04
1.92
22ºC
Capacity kW
10.95
8.68
7.28
6.58
6.18
5.48
5.12
Input kW.
3.38
2.68
2.22
2.11
2.01
1.93
1.78
27ºC
Capacity kW
9.48
7.59
6.31
5.68
5.37
4.78
4.45
Input kW.
2.92
2.32
1.95
1.83
1.76
1.65
1.58