3.2 Moisture Separator/Oil Removal Filter

NOTE:  Prepackaged maintenance kits are available that
include all necessary filter and timed drain valve
components. Maintain maximum performance and
efficiency with Genuine Parts. See page 18 for ordering
information.

When to replace the Separator/Filters

Replace filter element when pressure drop across
dryer is excessive or annually.

Dryers have the option of one or two stages of
filtration. The directions for servicing either filter is
identical.

When removing liquids at rated flow conditions, an
increase in pressure drop will occur as the separator/
filter elements become loaded with solid particles.

Procedure for Separator / Filter Element
Replacement 125-500 scfm models

THIS FILTER IS A PRESSURE CONTAINING

DEVICE. DEPRESSURIZE BEFORE SERVICING. If filter has not
been depressurized before disassembly, an audible alarm
will sound when the bowl begins to be removed from the
head. If this occurs, stop disassembly, isolate and
completely depressurize filter before proceeding.

200 thru 500 scfm models

Separator Element 
or Optional Oil Removal 
Element

Wave
Spring

Bowl
O-ring

Timer Drain Valve - Standard

3.0  MAINTENANCE

3.1 Condenser coil

A. Air-cooled - clean off accumulated dust and dirt

monthly or as necessary in dirty environments.

B.

Water-cooled - clean strainer monthly, more often if
required. Shut off water, remove small plug to relieve
pressure, then remove large plug to remove strainer.
Clean strainer and replace.

125 thru 150 scfm Models

Separator Element or
Optional Oil Removal Element

Timer Drain Valve - Standard with I-Controller Level 2

Demand Drain - I-Controller Level 3 Only

1.

Isolate dryer (close inlet and outlet valves if installed)
or shut off air supply.

2.

Depressurize filter by slowly opening manual  drain
by-pass valve.

3.

Remove bowl

a.

For 125 through 150  scfm models - bayonet
mount - push bowl up, turn bowl 1/8th turn to
your left, and pull bowl straight down

b.

For 200 through 500 scfm models - threaded
bowls - unscrew bowl from head using hand,
strap wrench or C spanner.

4.

Clean filter bowl

5.

Replace moisture separator element.

a.

Replacing complete Grade B element.
1)  Pull off old element and discard
2)  Make certain o-rings on male of replacement

element adaptor are in place and push
element into filter head.

NOTE:  Do not  handle Oil Removal Filter elements by
outside foam cover. Handle by bottom end cap only.

6.

After making certain that o-ring inside  top of bowl
(and on bayonet mount heads, wave spring) are in
place, reassemble bowl to head.

NOTE:  Make certain o-ring is generously lubricated. (Use
lubricant provided)

NOTE:  Wave spring ends should be pointed down to
prevent the wave spring from interfering with
reassembly.

Summary of Contents for CRN Series

Page 1: ...7610 478 40D 040103 7610 478 40D 040103 INTERNAL USE ONLY 7610 721 74 1 04 CA18 2 650 1st Ed 7610 478 40D 040103 INTERNAL USE ONLY CRN300 CRN400 CRN500 CRN750 GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 4 7 3 0 MAINTENANCE 8 9 SIZING 10 ENGINEERING DATA 11 ELECTRICAL SCHEMATICS 12 13 DIMENSIONS WEIGHTS 14 15 TROUBLESHOOTING 16 17 PARTS LIST 18 WARRANT...

Page 2: ...age be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found upon unpacking notify the carrier immediately and insist on his agent inspecting the shipment Concealed damage claims are not our responsibility as our terms are F O B point of shipment C MOVING In m...

Page 3: ...Piping connections A Air Inlet Connect compressed air line from air source to air inlet Reference markings on dryer or see callout drawing on pages 14 and 15 for air in outlet connection locations Refer to Serial Number Tag for maximum working pressure Do not exceed dryer s Maximum Working Pressure NOTE Install dryer in air system at highest pressure possible e g before pressure reducing valves NO...

Page 4: ...alve slowly 7 Close air by pass valve 8 Identify I Controller version Level on dryer A Models with I Controller Level 2 proceed to Step 9 B For Models with I Controller Level 3 see Section 2 7 for further instructions 9 Toggle ON OFF switch to the ON position 1 4 Electrical connections IMPORTANT Use copper supply wires only A Dryer is designed to operate on the voltage phase and frequency listed o...

Page 5: ...ce the Minutes Between Drain Cycle LED s from left to right until reaching your selection The Red LED is not used Reference Table 2 for Drain Cycle Intervals 3 To initiate the new setting press the Drain Interval Program button this will store the new setting and exit the program 4 Exiting the Program will cause the Timer Drain to discharge and begin a new cycle NOTE Failure to perform step 3 with...

Page 6: ... Temp F C to Service IC3 Ver xxx 50 F 95 F 10 C Ambient Temp Total Set Language Eng English Ambient Set Pt 105 F F C Hours Spanish French 95 F 122 F 41 C Inlet Air Temp Set Date Current Inlet Air Set Pt 105 F F C MO DA YR 95 F 140 F 41 C HR MIN SEC Set Time Eastern Service Interval 2000 MO DA YR HR MIN SEC Standard 0 4000 Hours Hours Dryer SetTemp ON OFF F C F Table 1 Vacuum Fluorescent Text Displ...

Page 7: ...ing of the solenoid valve for a given period of time Once the time has elapsed the solid state processor transmits information to energize the coil in the solenoid valve 2 The magnetic force of the coil causes the solenoid core 3 to move closing the pilot air supply line and opening the pilot air exhaust line After the pilot air above the diaphragm 4 is vented pressure in the reservoir opens the d...

Page 8: ...thly or as necessary in dirty environments B Water cooled clean strainer monthly more often if required Shut off water remove small plug to relieve pressure then remove large plug to remove strainer Clean strainer and replace 125 thru 150 scfm Models Separator Element or Optional Oil Removal Element Timer Drain Valve Standard with I Controller Level 2 Demand Drain I Controller Level 3 Only 1 Isola...

Page 9: ...tructions j Install the new element by carefully pushing it in to the element sealing port 1a k Reinstall the element retainer plate 5 l Inspect the upper and lower shell cap gaskets and apply a thin coat of lubricant to the outside and to the sealing lips of these gaskets m Slide the separator shell assembly back in n Slide the gaskets into position centering them between the coupling grooves o R...

Page 10: ...city from Table 1 by the multipliers shown in Table 2 Example How many scfm can an air cooled 750 scfm model handle when compressed air to be dried is at 200 psig and 100 F ambient air temperature is 80 F and a 38 F dew point temperature is desired Answer 750 x 1 22 x 1 12 x 1 0 1 025 scfm TABLE 2 Air capacity correction factors Multipliers MODELS 125 150 200 250 300 400 500 750 Rated capacity 60 ...

Page 11: ... 7 Branch Circuit Fuse Size amps 24 15 20 25 45 Watts 35 F Evaporator 100 F Ambient 1060 1335 1940 2620 3600 Resistance Ohms Three phase Total 1 77 1 256 1 058 0 853 Single phase Start C S 3 15 Run C R 0 416 Nominal Voltage 208 230 1 60 460 3 60 460 3 60 460 3 60 460 3 60 Max Min Voltage 253 198 506 414 506 414 506 414 506 414 Rated Load Amps 8 3 4 0 4 9 6 2 11 Locked Rotor Amps 33 5 25 33 40 45 M...

Page 12: ...lay HTR CrankcaseHeater FM FanMotor OL Overload CUSTOMERCONNECTION POWERCORD SR CONPE CONPE BLU BLU 1 2 GROUND DRN1 DRN2 1 L N FM 2 FM FM FPS M R CONN NEUTRAL LINE BRN 2 BRN CONL1 1 CON L1 2 N N N 2 FM 1 L L SW 1 C L3 2 CAP SR S S MTR OL 1 3 NOTUSED ONWATER COOLEDUNITS COIL COMP ON DRAIN NEUTRAL DRAIN TC1 TB5 N L P IC2OPTION BOARDADDITIONANDDRAINS SEEOPTIONNOTES CUSTOMERCONNECTION POWERCORD SW FM ...

Page 13: ...3 TO TB PE L3 TB TO TB L2 L2 TO TB L1 L1 TRANSFORMER CONNECTION TR1 575V CONNECTION SHOWN H6 H1 X3 X1 X2 X4 H1 PE L3 L2 PE L3 L2 FOR USE TAPS 208V H6 H5 230V H6 H4 460V H6 H2 380 420V H6 H3 2 X 6 H 4 5 H H 2FU TB TB 9 A2 A1 INLET TEMP TB TB 6 10 TB 11 SEPARATOR TEMP IC3 CONTROL PANEL REMOTE START STOP AMBIENT TEMP 8 TB 9 TB 7 17 13 TB TB 12 TB 14 DRAIN TEST POWER ON FAULT 15 POWER 16 MTR TB TB TB ...

Page 14: ...6 26 32 3 8 32 3 8 D 4 1 8 4 1 8 5 5 16 5 5 16 E 9 7 16 9 7 16 12 5 8 12 5 8 F 4 1 2 4 1 2 4 4 G 20 11 16 20 11 16 24 7 16 24 7 16 H 24 3 16 24 3 16 21 3 16 21 3 16 I 24 24 29 3 4 29 3 4 J 21 13 16 21 13 16 27 1 8 27 1 8 Inlet Outlet Connections 1 MPT 1 MPT 1 1 2 MPT 1 1 2 MPT Weight lbs 229 244 410 410 Weight lbs with Oil Removal Filter 237 252 423 423 125 thru 150 scfm models 200 thru 250 scfm m...

Page 15: ... 33 9 16 33 9 16 38 3 4 H 37 9 16 37 9 16 37 9 16 42 3 4 I 44 3 4 44 3 4 44 3 4 48 3 4 J 27 1 8 27 1 8 27 1 8 27 1 16 Inlet Outlet Connections 1 1 2 MPT 2 MPT 2 1 2 MPT 2 1 2 MPT Weight lbs 631 672 701 968 Weight lbs with Oil Removal Filter 644 704 733 1038 TOP VIEW FRONT VIEW RIGHT SIDE VIEW 300 thru 500 scfm models 750 scfm models TOP VIEW FRONT VIEW RIGHT SIDE VIEW C J B A F G H E D C I J B A F...

Page 16: ...outlet temperature 2 Refrigeration system not func tioning properly resulting in high air outlet temperature 3 Dryer is running with no load a Power failure a ON OFF switch is OFF b Line disconnect switch open c Blown fuses open breaker d Faulty wiring loose terminals a High or low ambient conditions b Air cooled models Dirty clogged condenser fins obstructed air flow across condenser or non funct...

Page 17: ...MBIENT TEMP 1 Poor ventilation Ensure ventilation is adequate for heat load High Ambient Air Temperature Ensure compressor is not ventilated toward dryer ALERT INLET AIR TEMP 1 No aftercooler on compressor Install an aftercooler High Inlet Air Temperature 2 Dirty aftercooler Clean aftercooler 3 Poor Ventilation Ensure ventilation is adequate for heat load ALARM DEW POINT TEMP 1 Refrigerant leak Ha...

Page 18: ...481074146 Power Transformer 575 V C61202771 C61202771 C61202771 C61202771 C61202771 C61202771 C61202771 C61202771 Refrigerant High Pressure Switch watercooled C413013836 C413013836 C413013836 C413013836 C413013836 C413013836 C413013836 C413013836 SureSave Valve C413082943 C413082943 C413082943 C413082943 C413082943 C413082943 C413082943 C413082943 OnOff Switch C611070613 C611070613 C611070613 C611...

Page 19: ...19 NOTES ...

Page 20: ...GE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER REPORT REPAIR OR MODIFY LATENT DEFECTS INHERENT THEREIN THE MANUFACTURER HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS EXPENSES OR DAMAGES INCURRED BY TH...

Reviews: