201004 - 7500W WIRELESS REMOTE START GENERATOR
OPERATION
25
Do Not Overload Generator
Never exceed the specified capacity when adding loads to the
generator. Each individual receptacles is protected against
overload by a circuit breaker. If the amperage of any circuit
breaker exceeds its rating, the circuit breaker opens and the
electrical output to that receptacle is lost. If a 30A circuit breaker
opens, the 20A receptacle will also lose electrical output. Remove
the load from the receptacle and reset the open circuit breaker to
restore electrical output.
Capacity
Follow these simple steps to calculate the running and starting
watts necessary for your purposes:
1. Select the electrical devices you plan on running at the same
time.
2. Total the running watts of these items. This is the amount of
power you need to keep your items running.
3. Identify the highest starting wattage of all devices identified
in step 1. Add this number to the number calculated in step 2.
Starting wattage is the surge of power needed to start some
electric driven equipment. Following the steps listed under
“Power Management” will guarantee that only one device will
be starting at a time.
Power Management
Use the following formula to convert voltage and amperage to
watts:
Volts × Amps = Watts
To prolong the life of your generator and attached devices, follow
these steps to add electrical load:
1. Start the generator with no electrical load attached.
2. Allow the engine to run for several minutes to get up to
temperature.
3. Plug in and turn on the first item. It is best to attach the item
with the largest load first.
4. Allow the engine to stabilize.
5. Plug in and turn on the next item.
6. Allow the engine to stabilize.
7. Repeat steps 5-6 for each additional item.
GfCI
Your generator is equipped with ground fault circuit interrupter
(GFCI) receptacles. In the event of a ground fault, a GFCI trips
automatically to stop the flow of electricity and prevent serious
injury. The green indicator light (A) on the receptacle will also
turn off. Press the “RESET” (B) button located on the front of the
receptacle to restore flow of electricity. The indicator light will also
turn back on. GFCI does not protect against circuit overloads.
To ensure proper operation of the GFCI duplex, perform this test
monthly:
1. With the generator running, plug a lamp into the GFCI
receptacle. Turn the lamp on.
2. Press the “TEST” (C) button located on the front of the
receptacle to trip the device. This should immediately stop
the flow of electricity and shut off the lamp. If the electricity
is not stopped, do not use this receptacle until it has been
serviced or replaced.
3. Press the “RESET” button located on the front of the
receptacle to restore the flow of electricity. If the indicator
light does not come back on or if the GFCI cannot be reset
then it must be replaced.
A
C
b
NOTICE
In any electrical application, some current will flow through
the protective ground conductor to the ground, this is called
leakage current. It takes 4 mA (0.004 A) and higher of leakage
current from the hot wire to the ground to cause a GFCI to trip.
On circuits protected by GFCI’s, leakage current can cause
unnecessary and intermittent tripping.
Some stationary motors, such as a bathroom vent fan,
fluorescent lighting fixtures or some refrigerators, may produce
enough leakage to cause nuisance tripping. To avoid nuisance
tripping, a GFCI should not supply:
–
Fluorescent or other types of electric-discharge lighting
fixtures.
–
Permanently installed electric motors, like air conditioners,
furnaces or refrigerators.
Stopping the Engine
Remote Stop
1. Turn off all electrical connected loads. Never start or stop the
generator with electrical devices turned on.
2. Let the generator run at no-load for several minutes to
stabilize internal temperatures of the engine and generator.