SECTION 2 / INSTALLATION
INSTRUCTIONS
IMPORTANT NOTICE
These instructions are intended for the use of quali-
fied personnel only, specifically trained and experi-
enced in the installation of this type of heating equip-
ment and related system components. Installation
and service personnel must be CORGI registered.
Persons not qualified must not attempt to fix this
equipment nor attempt repairs according to these
instructions.
WARNING:
Improper installation, adjustment, alteration, service
or maintenance may damage the equipment, create
a hazard resulting in asphyxiation, explosion or fire,
and will void the warranty.
STATUTORY REQUIREMENTS
Gas Safety (Installation and Use)
Regulations, 1994
It is the law that all gas appliances are installed by
competent persons in accordance with the above
regulations. Failure to install appliances correctly
could lead to prosecution. It is in your own interest,
and that of safety, to ensure that the law is complied
with.
General Requirements
The appliance must be installed by a competent
person ie. CORGI registered in accordance with the
relevant requirements of the Gas Safety Regulations,
current I.E.E. Regulations, Model Water Byelaws,
Local Water Authority Byelaws and any relevant
requirements of the local gas supplier, local authority
and the relevant British Standard Codes of practice
and Building Regulations. Manufacturers notes must
not be taken in any way as overriding statutory
obligations. Typical documents include:
Models 055, 105 & 155
BS. 5440:1
Flues (for gas appliances of rated input not
exceeding 60 KW).
BS. 5440:2
Ventilation (for gas appliances of rated input not
exceeding 60KW).
BS. 5449
Forced circulation hot water systems.
BS. 6798
Installation of gas fired hot water boilers of
rated input not exceeding 60 KW.
BS. 6891:
Installation of low pressure pipework.
Health & Safety Document No. 635.
The Electricity at Work regulations, 1989.
CP341; Water Supply.
British Gas Publications:
IM2; Purging Procedures of Non-domestic Gas Installations
IM5, Soundness Testing Procedures for Industrial and
Commercial Gas Installations.
8
01-10-98
Sheet Metal
24 Gauge
0.7mm
12" Min.
300mm
12" Min.
300mm
4" Min.
100mm
Hollow concrete cinder block, align holes and
leave ends open. Alternative method for providing
a non-combustible base.
Models 185, 265 & 405
BS. 6891;
Installation of low pressure pipework.
BS. 6644;
Installation of Gas Fired Hot Water
Boilers 60kW to 2MW.
CP 341;
Water Supply.
British Gas Publications:
IM2;
Purging Procedures on Non-domestic
Gas Installations.
IM5;
Soundness Testing Procedures for
Industrial and Commercial Gas Installations.
IM11;
Flues for Commercial and Industrial
Gas Fired Boilers and Air Heaters.
Model Water Byelaws.
This appliance must be installed externally in open air
(without a flue) or indoors (with a suitable flue system)
in a room separated from living rooms and provided
with appropriate ventilation direct to the outside.
The appliance must be used only in accordance with
these instructions. Incorrect use is dangerous and
invalidates all warranties and Certification.
Conversion Instructions.
The heater is supplied in two versions,one for use
with Natural Gas, G20 at 20 mbar inlet pressure, the
other for Propane, G31 at 37 mbar. If it is necessary
to convert the heater for use on the other gas the
appropriate conversion kit must be purchased and
fitted using the instructions provided.
NOTE:
The heater should not be located in an area
where possible water leakage will result in damage
to
the area adjacent to the appliance or to the
structure. When such locations cannot be
avoided, it is recommended that a suitable drain pan,
adequately drained, be installed under the appliance.
The pan must not restrict combustion air flow.
BASE INSTALLATION
Heater must be mounted on a level base, such as
cement slab, cement blocks or other non-combus-
tible surface. An alternative method for providing a
base for combustible floors is illustrated below.
Heaters must
not
be installed on carpeting.
base.tif