EliteIQ
TM
User Manual
67
9M02-7100-A001-EN
Version B
Item
Description
Relay State to High
Alarm
Specify the relay behavior when the input transitions to the High Alarm:
0 – De-energize
1 – Energize
2 – No change (disabled)
Relay State to Low
Alarm
Specify the relay behavior when the input transitions to the Low Alarm:
0 – De-energize
1 – Energize
2 – No change (disabled)
Repeat Interval
Number of minutes until this action is performed again.
[0-1440 minutes] (default is 1440 minutes).
0 is never.
Reset Counters
Selection 7 under System setup.
Allows the user to reset one or all counters for a channel.
Reset Key
Reset this entry to the factory default.
Reset to System
Defaults
Performing this function erases all user programming and sets the system back to
the factory settings.
Note:
This is only written to permanent memory when the EliteIQ is put into
RUN mode. If you do not want to reset the system, turn the EliteIQ off
before
returning to RUN mode.
Hidden underneath this function is a method to Backup and Restore a complete
programmed configuration. Enter ‘9’ and then the access code (*42552) to enable
this function.
Restore
See Reset to System Defaults.
RS-485
Port 2 or 3 can be used as either a RS-232 or RS-485 connection. If RS-485 is
enabled, then the 6-position connector on the top-back of the large processor
board (location J17) is used for communication.
Note:
Do not connect to both the RS-232 and the RS-485.
RS-485 Off Delay
Specifies in milliseconds that amount of time the EliteIQ waits after sending the
last character of a transmission until it turns off the RS-485 transceiver (goes to
the tri-state condition).
RS-485 On Delay
Specifies in milliseconds that amount of time the Elite waits after turning the
RS-485 transceiver on before it transmits the first character of a transmission.
RUN Mode
In this mode, the EliteIQ is monitoring all inputs and performing all alarm
functions.
Note:
This mode must be entered after making programming changes for
those changes to be saved permanently.