EliteIQ
TM
User Manual
63
9M02-7100-A001-EN
Version B
Item
Description
Options Setup
This Menu has eight selections to set the various Options that can be purchased
with the EliteIQ.
Option Number Description
0
Port 1 LTE modem port setup
1
Port 2 Setup
2
Port 3 Setup
3
Modem Setup
4
Modbus Master Setup
5
Open Loop Limit
Analog Input Scaling Factor
Analog Input Offset Factor
6
Acknowledge Input Channel
7
Pump Control (see separate product manual)
Port Mode
For serial ports 2 and 3, the Mode defines how the port is going to be used.
0 – Not used
1 – Debug or diagnostics
2 – Not used
3 – Modbus Master
4 – Not used
Ports
The available ports in the EliteIQ are as follows:
0 – UART used for LTE modem
1 – Port 2
2 – Port 3
Positive Rate of Change
If the analog reading rises at a rate that exceeds the Positive Rate of Change
within the time specified by the Rate of Change Period, then the channel goes into
alarm.
For example, if the Positive Rate of Change is set to 100.00 and the Rate of
Change Period is set to 15 minutes, then if the analog reading exceeds 100.00 in
less than 15 minutes, the channel goes into alarm.
Power Fail
See Primary Power Channel.
Primary Power Channel
Channel 01 – monitors the primary power to the main processor board. This
power is typically 24 VDC. Low and High alarm limits can be specified for alarm
relay activation or call outs. The Primary Power LED indicates if the battery is fully
charged (green), being charged (green blinking), or in alarm (red and red blinking).