Item
Description
Zero Scale
The scaling value in engineering units that corresponds to the lowest analog
reading.
This value can be positive (+) or negative (-). When entering this value, pressing
the ‘*’ key twice toggles between (+) and (-).
For example, for a 4-20 mA signal that goes from 20.0 to 200.0, the Zero Scale is
the value at 4 mA. It is entered as 200 with the Decimal Position set to 1.
Relay Channels
Channel Number
11 – 98
Pulse Duration (0)
Seconds
Channel Mode (2)
0 – disable, 1 – status only (enabled)
Channel Name (4)
Relay Lists
Relay List Number
01 - 98
Position 1 Relay Channel (1)
11 – 98
Position 2 Relay Channel (2)
Position 3 Relay Channel (3)
Position 4 Relay Channel (4)
Position 5 Relay Channel (5)
Position 6 Relay Channel (6)
Position 7 Relay Channel (7)
Position 8 Relay Channel (8)
Position 9 Relay Channel (9)