![Carrier WEATHERMASTER 50HJQ016 Product Data Download Page 95](http://html.mh-extra.com/html/carrier/weathermaster-50hjq016/weathermaster-50hjq016_product-data_2560349095.webp)
95
COOLING CAPACITIES (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leav-
ing indoor coil (h
lwb
)
Where: h
ewb
= Enthalpy of air entering indoor coil
3. SHC is based on 80 F edb temperature of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
50HJQ012 (10 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/BF
3000/0.03
4000/0.04
5000/0.06
Indoor Entering Air — Ewb (F)
72
67
62
72
67
62
72
67
62
75
TC
136.0
124.0
111.4
141.2
129.0
116.6
145.6
132.0
121.2
SHC
64.6
80.8
96.0
71.2
92.4
111.8
78.6
103.2
121.0
kW
7.51
7.35
7.20
7.61
7.45
7.29
7.72
7.53
7.39
85
TC
132.6
119.6
106.6
137.6
124.4
112.0
140.4
127.4
118.0
SHC
63.6
79.2
94.0
70.6
91.4
110.0
77.0
102.6
118.0
kW
8.40
8.23
8.09
8.50
8.33
8.17
8.58
8.40
8.27
95
TC
127.8
114.6
99.4
133.2
119.4
107.2
136.2
121.8
114.2
SHC
62.2
77.6
90.8
69.6
89.8
107.0
76.8
101.2
113.8
kW
9.36
9.18
9.01
9.48
9.30
9.15
9.56
9.36
9.24
105
TC
122.4
108.8
92.0
127.4
113.6
101.4
130.4
116.0
109.6
SHC
60.4
75.4
87.4
68.0
88.0
101.4
75.4
99.4
109.4
kW
10.41
10.26
10.02
10.53
10.35
10.22
10.63
10.43
10.35
115
TC
116.8
101.8
86.6
121.2
106.6
94.8
123.6
109.2
104.6
SHC
58.6
72.8
84.6
66.0
85.4
94.8
73.4
97.0
104.6
kW
11.58
11.37
11.15
11.68
11.51
11.35
11.76
11.60
11.51
125
TC
110.6
95.8
84.6
114.6
98.4
88.8
117.0
100.8
96.4
SHC
56.4
70.6
83.4
64.4
82.4
88.8
71.4
93.8
96.4
kW
12.87
12.62
12.36
12.97
12.73
12.60
13.03
12.83
12.77
50HJQ014 (12
1
/
2
Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/BF
3750/0.04
4500/0.05
5000/0.05
5625/0.06
6250/0.07
Indoor Entering Air — Ewb (F)
72
67
62
72
67
62
72
67
62
72
67
62
72
67
62
75
TC
167.0
154.0
140.0
171.0
158.0
144.0
173.0
159.0
146.0
171.0
162.0
148.0
173.0
161.0
151.0
SHC
79.6
100.0
120.0
85.0
108.0
131.0
87.5
114.0
138.0
94.5
120.0
146.0
97.7
127.0
150.0
kW
10.00
9.77
9.50
10.10
9.87
9.61
10.20
9.93
9.68
10.20
10.00
9.74
10.20
10.00
9.80
85
TC
160.0
148.0
133.0
164.0
151.0
137.0
167.0
154.0
140.0
168.0
155.0
143.0
166.0
157.0
146.0
SHC
77.6
98.9
118.0
82.0
107.0
129.0
86.1
113.0
136.0
89.6
118.0
142.0
95.3
125.0
146.0
kW
11.10
10.80
10.40
11.20
10.90
10.60
11.30
11.00
10.70
11.30
11.00
10.80
11.30
11.10
10.80
95
TC
155.0
141.0
127.0
157.0
144.0
131.0
160.0
146.0
133.0
161.0
149.0
137.0
163.0
149.0
140.0
SHC
76.1
96.3
115.0
80.3
105.0
126.0
84.4
110.0
132.0
86.5
117.0
137.0
91.7
121.0
140.0
kW
12.20
11.80
11.40
12.20
11.90
11.50
12.40
12.00
11.60
12.40
12.10
11.80
12.50
12.10
11.90
105
TC
147.0
133.0
120.0
150.0
137.0
124.0
152.0
138.0
127.0
153.0
140.0
131.0
154.0
141.0
134.0
SHC
73.6
93.3
112.0
78.5
102.0
123.0
81.6
108.0
127.0
85.1
114.0
131.0
88.6
120.0
134.0
kW
13.20
12.70
12.30
13.30
12.90
12.50
13.40
13.00
12.60
13.50
13.10
12.80
13.50
13.10
12.90
115
TC
140.0
126.0
112.0
141.0
129.0
118.0
144.0
130.0
121.0
144.0
131.0
125.0
146.0
133.0
128.0
SHC
71.4
90.3
109.0
75.1
99.1
117.0
78.9
104.0
121.0
81.9
110.0
125.0
87.0
117.0
128.0
kW
14.20
13.70
13.20
14.30
13.90
13.50
14.40
14.00
13.70
14.50
14.00
13.90
14.60
14.10
14.00
125
TC
131.0
118.0
105.0
134.0
120.0
111.0
135.0
122.0
115.0
137.0
123.0
118.0
136.0
124.0
121.0
SHC
68.1
87.6
105.0
73.5
96.4
111.0
75.7
102.0
115.0
80.7
108.0
118.0
83.4
113.0
121.0
kW
15.20
14.70
14.10
15.40
14.90
14.50
15.40
14.90
14.70
15.60
15.00
14.90
15.60
15.10
15.00
BF
—
Bypass Factor
Edb —
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW
—
Compressor Motor Power Input
SHC —
Gross Sensible Heat Capacity (1000 Btuh)
TC
—
Gross Total Capacity (1000 Btuh)
t
ldb
= t
edb
–
sensible capacity (Btuh)
1.10 x cfm
h
lwb
= h
ewb
–
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
under 75
81
82
83
84
85
over 85
Correction Factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
shown below.
.10
.98
1.96
2.94
3.92
4.90
.20
.87
1.74
2.62
3.49
4.36
.30
.76
1.53
2.29
3.05
3.82
50
HJ
Q
Summary of Contents for WEATHERMASTER 50HJQ016
Page 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Page 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Page 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Page 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Page 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...