28
INSTANTANEOUS AND INTEGRATED HEATING RATINGS (cont)
LEGEND
NOTES:
1.
indicates integrated ratings.
2. Integrated capacity is maximum (instantaneous) capacity less the
effect of frost on the outdoor coil and the heat required to defrost it.
50TFQ007
Return
Air
(F db)
Cfm
(Standard
Air)
Air Temperature Entering Outdoor Coil (F)
0
10
17
30
40
47
50
60
55
1800
Cap.
37.8
32.2
43.9
40.3
48.3
44.1
58.0
50.8
66.2
66.2
72.3
72.3
75.2
75.2
86.0
86.0
kW
4.72
4.97
5.16
5.58
5.96
6.25
6.40
6.95
2400
Cap.
37.9
32.2
44.0
40.4
48.5
44.2
58.4
51.2
66.6
66.6
72.8
72.8
75.9
75.9
87.0
87.0
kW
4.55
4.76
4.92
5.28
5.57
5.81
5.93
6.38
3000
Cap.
38.0
32.3
44.0
40.4
48.5
44.3
58.5
51.3
66.9
66.9
73.1
73.1
76.2
76.2
87.5
87.5
kW
4.46
4.64
4.78
5.09
5.35
5.56
5.67
6.07
70
1800
Cap.
37.3
31.7
43.6
40.0
48.1
43.9
57.5
50.4
65.2
65.2
71.1
71.1
74.0
74.0
84.6
84.6
kW
5.32
5.61
5.84
6.33
6.75
7.10
7.27
7.91
2400
Cap.
37.5
31.9
43.8
40.2
48.2
43.9
57.7
50.5
65.6
65.6
71.8
71.8
74.7
74.7
85.4
85.4
kW
5.13
5.38
5.57
5.97
6.32
6.61
6.74
7.25
3000
Cap.
37.6
32.0
43.9
40.3
48.3
44.0
57.8
50.7
66.0
66.0
72.1
72.1
75.0
75.0
86.0
86.0
kW
5.03
5.25
5.41
5.76
6.08
6.32
6.44
6.89
80
1800
Cap.
36.8
31.3
43.1
39.6
47.9
43.7
57.1
50.1
64.8
64.8
70.5
70.5
73.4
73.4
83.6
83.6
kW
5.75
6.09
6.34
6.88
7.35
7.72
7.90
8.58
2400
Cap.
37.0
31.4
43.4
39.8
48.0
43.8
57.4
50.3
65.1
65.1
71.1
71.1
73.9
73.9
84.5
84.5
kW
5.55
5.83
6.04
6.49
6.87
7.18
7.33
7.89
3000
Cap.
37.1
31.5
43.5
39.9
48.1
43.9
57.5
50.4
65.3
65.3
71.5
71.5
74.4
74.4
85.0
85.0
kW
5.44
5.68
5.87
6.26
6.60
6.88
7.01
7.49
50TFQ008
Return
Air
(F db)
Cfm
(Standard
Air)
Air Temperature Entering Outdoor Coil (F)
0
10
17
30
40
47
50
60
55
2000
Cap.
36.6
31.2
44.0
40.4
49.8
45.4
61.4
53.8
70.4
70.4
77.4
77.4
80.6
80.6
91.8
91.8
kW
5.24
5.64
5.94
6.58
7.08
7.50
7.68
8.32
2600
Cap.
37.6
32.0
45.2
41.4
51.2
46.6
63.0
55.2
72.4
72.4
79.6
79.6
83.0
83.0
92.4
92.4
kW
5.18
5.56
5.82
6.40
6.84
7.20
7.36
7.78
3200
Cap.
38.2
32.4
45.8
42.0
51.8
47.2
63.8
55.8
73.6
73.6
81.0
81.0
83.8
83.8
91.2
91.2
kW
5.16
5.50
5.74
6.28
6.70
7.02
7.12
7.40
70
2000
Cap.
32.4
27.6
40.4
37.2
46.0
41.8
57.8
50.6
66.8
66.8
73.6
73.6
76.6
76.6
87.8
87.8
kW
5.42
5.90
6.22
6.92
7.48
7.94
8.16
8.90
2600
Cap.
33.4
28.4
41.8
38.2
47.4
43.2
59.6
52.2
68.8
68.8
75.8
75.8
79.0
79.0
90.4
90.4
kW
5.38
5.82
6.12
6.76
7.28
7.68
7.86
8.48
3200
Cap.
34.2
29.0
42.2
38.6
48.4
44.0
60.6
53.0
70.0
70.0
77.2
77.2
80.6
80.6
91.0
91.0
kW
5.36
5.76
6.06
6.66
7.14
7.50
7.68
8.16
80
2000
Cap.
29.2
24.8
37.4
34.4
43.4
39.6
54.8
48.0
64.0
64.0
70.8
70.8
73.8
73.8
84.8
84.8
kW
5.52
6.02
6.40
7.12
7.72
8.22
8.44
9.24
2600
Cap.
30.2
25.8
38.8
35.6
44.6
40.6
56.8
49.8
66.2
66.2
73.2
73.2
76.4
76.4
87.8
87.8
kW
5.48
5.96
6.30
6.98
7.54
7.98
8.18
8.88
3200
Cap.
31.0
26.4
39.6
36.4
45.4
41.4
58.0
50.8
67.4
67.4
74.6
74.6
78.0
78.0
89.0
89.0
kW
5.46
5.92
6.24
6.90
7.42
7.82
8.00
8.58
Cap. —
Heating Capacity (1000 Btuh) (includes indoor-fan motor heat)
db
—
dry bulb
kW
—
Total Power Input (includes compressor motor power input,
outdoor-fan motor input, and indoor-fan motor input)
Performance data — 50TFQ (cont)
50
TF
Q
Summary of Contents for WEATHERMASTER 50HJQ016
Page 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Page 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Page 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Page 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Page 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...