PremierLink™ Direct Digital controls —
The Premier-
Link Direct Digital Controls (DDC) requires the use of a
Carrier electronic thermostat or a CCN connection for
time broadcast to initiate its internal timeclock. This is nec-
essary for broadcast of time of day functions (occupied/
unoccupied).
PremierLink Features:
• Equipment Control Functions
Cooling Stages
Heating Stages
Indoor-Fan Motor
4-Way Valve
• EconoMi$er2 Control Functions
Dry Bulb Control
Enthalpy Control
Differential Enthalpy
Power Exhaust
• Advanced Control Functions
Smoke Detection
Optimal Start (90.1)
Unoccupied Free Cool
Smart Staging and Optimal Staging
• Network Protocol
CCN
Internet Ready 38.4 baud rate
• Diagnostics/Advanced Service Features
Diagnostics
Onboard display
• Scheduling
Via Communicating Stat
• User Interface
Navigator (LEN protocol)
LID2B (CCN)
PC with Carrier software (CCN)
DESCRIPTION
STATUS
UNITS
POINT
LIMITS
ACCESS
Space Temperature
xxx.x
dF
SPT
-40.0 to 245.0 dF
R/W
Supply Air Temperature
xxx.x
dF
SAT
-40.0 to 245.0 dF
R/W
Outside Air Temperature
xxx.x
dF
OAT
-40.0 to 245.0 dF
R/W
Control Setpoint
xxx.x
dF
CLSP
R
Cooling % Total Capacity
xxx
%
CCAP
0 to 100 %
R
Heating % Total Capacity
xxx
%
HCAP
0 to 100 %
R
EconoMi$er2 Active
No/Yes
ECOS
0 to 1
R
Supply Fan Relay
Off/On
SF
0 to 1
R/W
Supply Fan Status
Off/On
SFS
0 to 1
R
Economizer Position
xxx.x
%
ECONPOS
0.0 to 100.0 %
R/W
Current Min Damper Pos
xxx.x
%
IQMP
0.0 to 100.0 %
R
Filter Status
Clean/Dirty
FLTS
0 to 1
R/W
Remote Occupied Mode
Off/On
RMTOCC
0 to 1
R/W
Heat Stage 1
Off/On
HS1
0 to 1
R
Heat Stage 2
Off/On
HS2
0 to 1
R
Heat 3/Exhaust/Rev Valve
Off/On
H3_EX_RV
0 to 1
R
Enthalpy
Low/High
ENTH
0 to 1
R/W
Indoor Air Quality
xxxx.x
IAQI
0.0 to 5000.0
R/W
Indoor Air Quality Setpt
xxxx.x
IAQS
0.0 to 5000.0
R
Outdoor Air Quality
xxxx.x
OAQ
0.0 to 5000.0
R/W
Fire Shutdown
Normal/Alarm
FSD
0 to 1
R/W
SPT Offset
xx.x
^F
STO
-15.0 to 15.0 ^F
R/W
Compressor 1
Off/On
CMP1
0 to 1
R
Compressor 2
Off/On
CMP2
0 to 1
R
Compressor Safety
Off/On
CMPSAFE
0 to 1
R
Controls
Summary of Contents for WEATHERMASTER 50HJQ016
Page 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Page 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Page 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Page 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Page 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...