ELECTRIC HEATING CAPACITIES — 50HJQ004-014
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW
new
= Heater kW rated x (unit power distribution voltage/rated heater voltage)
2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW
new
= 16 kW (215/240)
2
kW
new
= 12.8 kW (rating at 215 v)
UNIT
50HJQ
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY HEATER
PART NUMBER
CRHEATER---A00
SINGLE POINT BOX
PACKAGE NO.
CRSINGLE---A00
004
(3 Tons)
208/230/240
(single phase)
3.3/ 4.0/ 4.4
4.9/ 6.0/ 6.5
6.5/ 8.0/ 8.7
7.9/ 9.6/10.5
9.8/12.0/13.0*
001
002
003
004
002 & 002
—
—
004
004
005
208/230/240
(3 phase)
3.3/ 4.0/ 4.4
4.9/ 6.0/ 6.5
6.5/ 8.0/ 8.7
7.9/ 9.6/10.5
12.0/14.7/16.0
001
002
003
004
005
—
—
—
—
002
460/480
(3 phase)
5.5/ 6.0
8.1/ 8.8
10.6/11.5
12.9/14.0
006
007
008
009
—
—
—
—
005
(4 tons)
208/230/240
(single phase)
3.3/ 4.0/ 4.4
6.5/ 8.0/ 8.7
9.8/12.0/13.0*
13.1/16.0/17.4*
15.8/19.3/21.0*
001
003
002 & 002
003 & 003
004 & 004
—
004
005
005
005
208/230/240
(3 phase)
4.9/ 6.0/ 6.5
6.5/ 8.0/ 8.7
12.0/14.7/16.0
15.8/19.3/21.0*
002
003
005
004 & 004
—
—
002
003
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
006
008
009
008 & 008
—
—
—
—
006
(5 Tons)
208/230/240
(single phase)
4.9/ 6.0/ 6.5
6.5/ 8.0/ 8.7
9.8/12.0/13.0*
13.1/16.0/17.4*
15.8/19.3/21.0*
002
003
002 & 002
003 & 003
004 & 004
004
004
005
005
005
208/230/240
(3 phase)
4.9/ 6.0/ 6.5
7.9/ 9.6/10.5
12.0/14.7/16.0
15.8/19.3/21.0*
19.9/24.3/26.5*
002
004
005
004 & 004
004 & 005
—
002
002
003
002
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
23.4/25.5*
006
008
009
008 & 008
008 & 009
—
—
—
—
—
007
(6 tons)
208/230/240
(3 phase)
4.9/ 6.0/ 6.5
7.9/ 9.6/10.5
12.0/14.7/16.0
15.8/19.3/21.0*
19.9/24.3/26.5*
002
004
005
004 & 004
004 & 006
—
002
002
003
003
460/480
(3 phase)
5.5/ 6.0
10.6/11.5
12.9/14.0
21.1/23.0*
23.4/25.5*
006
008
009
008 & 008
008 & 009
—
—
—
—
—
Performance data — 50HJQ (cont)
50H
JQ
Summary of Contents for WEATHERMASTER 50HJQ016
Page 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Page 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Page 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Page 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Page 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...