FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)
LEGEND
*Standard drive range is 817 to 1038 rpm. Alternate drive range is 1082
to 1303. Other rpms may require a field-supplied drive.
NOTES:
1. Maximum continuous bhp is 5.90 and maximum continuous watts
are 5180. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
2. Fan performance is identical for horizontal discharge applications
using horizontal adapter curb (CRRFCURB013A00).
3. See this page for General Fan Performance notes.
GENERAL NOTES FOR FAN PERFORMANCE TABLES
1. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. For additional information on motor performance, refer
to Indoor-Fan Motor Performance table on page 126.
2. Values include losses for filters, unit casing, and wet coils. See
page 127 for accessory/FIOP static pressure information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
4. Interpolation is permissible. Do not extrapolate.
50HJQ016 (15 TONS)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
4500
584
717
0.8
695
952
1.1
798
1205
1.3
893
1483
1.7
984
1786
2.0
4800
609
839
0.9
717
1085
1.2
815
1346
1.5
907
1630
1.8
994
1938
2.2
5100
634
971
1.1
738
1229
1.4
833
1500
1.7
921
1791
2.0
1006
2104
2.4
5400
660
1118
1.3
760
1389
1.6
852
1669
1.9
937
1968
2.2
1019
2286
2.6
5700
687
1284
1.4
783
1566
1.8
873
1858
2.1
956
2165
2.4
1034
2490
2.8
6000
712
1458
1.6
805
1752
2.0
892
2055
2.3
973
2371
2.7
1049
2703
3.0
6300
736
1644
1.8
826
1952
2.2
911
2265
2.5
990
2591
2.9
1064
2930
3.3
6600
763
1856
2.1
851
2176
2.4
933
2502
2.8
1010
2837
3.2
1082
3186
3.6
6900
788
2078
2.3
873
2410
2.7
954
2747
3.1
1029
3093
3.5
1099
3451
3.9
7200
813
2316
2.6
896
2662
3.0
975
3011
3.4
1048
3367
3.8
1117
3734
4.2
7500
841
2584
2.9
921
2943
3.3
998
3304
3.7
1070
3672
4.1
1137
4049
4.5
50HJQ016 (15 TONS)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
4500
1070
2113
2.4
1151
2458
2.8
1229
2819
3.2
1302
3194
3.6
—
—
—
4800
1078
2269
2.5
1157
2620
2.9
1233
2990
3.3
1306
3374
3.8
—
—
—
5100
1086
2439
2.7
1164
2795
3.1
1238
3170
3.5
—
—
—
—
—
—
5400
1097
2626
2.9
1172
2986
3.3
1245
3366
3.8
—
—
—
—
—
—
5700
1110
2835
3.2
1183
3200
3.6
1253
3584
4.0
—
—
—
—
—
—
6000
1122
3053
3.4
1193
3422
3.8
1262
3810
4.3
—
—
—
—
—
—
6300
1135
3286
3.7
1204
3660
4.1
1271
4052
4.5
—
—
—
—
—
—
6600
1151
3549
4.0
1218
3928
4.4
1283
4325
4.8
—
—
—
—
—
—
6900
1167
3821
4.3
1232
4207
4.7
1295
4608
5.2
—
—
—
—
—
—
7200
1183
4113
4.6
1246
4505
5.0
—
—
—
—
—
—
—
—
—
7500
1202
4437
5.0
1264
4837
5.4
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower Input to Fan
FIOP —
Factory-Installed Option
Watts —
Input Watts to Motor
50
HJ
Q
Summary of Contents for WEATHERMASTER 50HJQ016
Page 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Page 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Page 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Page 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Page 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...