139
50HJQ014,016
LEGEND
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v and
600 v. If power distribution voltage to unit varies from rated heater voltage,
heater kW will vary accordingly.
†Fuse or HACR circuit breaker. This is the maximum size permissible; smaller
fuse size may be used where conditions permit.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The Canadian units may be
fuse or circuit breaker.
2. MCA calculation for units with electric heaters over 50 kW
= (1.25 x IFM amps) + (1.00 x heater FLA).
UNIT
50HJQ
VOLTAGE
(3 PH, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OUTDOOR
FAN
MOTOR
INDOOR FAN
MOTOR
POWER
EXHAUST
ELECTRIC HEAT*
POWER SUPPLY
DISCONNECT
SIZING
No. 1
No. 2
Min
Max
RLA
LRA
RLA
LRA
Qty
FLA
(ea)
Hp
FLA
FLA
LRA
FLA
kW
MCA
MOCP†
RLA
LRA
014
208/230
187
253
39.7
228
—
—
3
1.7
3.7
10.5/10.5
—
—
—/—
—/—
65/ 65
100/100
64/ 64
387/387
39/ 45
14/19
114/122
125/150
64/ 64
72/ 92
26/34
155/168
175/175
94/107
117/135
42/56
211/200
225/225
147/167
4.6
18.8
—/—
—/—
70/ 70
100/100
69/ 69
406/406
39/ 45
14/19
119/126
125/150
69/ 69
72/ 82
26/34
159/173
175/175
100/112
117/135
42/56
216/205
225/225
152/173
460
414
508
19.9
114
—
—
3
0.8
3.7
4.8
—
—
—
—
32
50
31
189
18
15
54
60
31
39
32
81
90
50
66
55
98
110
82
2.3
6.0
—
—
34
50
34
195
18
15
57
70
34
39
32
83
90
53
66
55
100
110
84
575
518
632
16.0
91
—
—
3
0.75
3.0
3.9
—
—
—
—
26
40
26
91
37
37
72
80
47
2.1
4.8
—
—
28
40
28
96
37
37
75
80
50
016
208/230
187
253
28.2
160
28.2
160
3
1.7
5
15.8/158
—
—
—/—
—/—
84/ 84
110/110
89/ 89
499/485
72/ 82
26/34
174/187
175/200
101/112
117/135
42/56
231/219
250/225
153/173
4.6
18.8
—/—
—/—
89/ 89
110/110
94/ 94
518/504
72/ 82
26/34
179/191
200/200
106/118
117/135
42/56
235/224
250/225
158/179
460
414
508
14.1
80
14.1
80
3
0.8
5
7.9
—
—
—
—
42
50
44
238
39
32
91
100
54
66
55
108
110
85
2.3
6.0
—
—
44
50
47
244
39
32
93
100
57
66
55
110
125
88
575
518
632
11.3
64
11.3
64
3
0.75
5
6.0
—
—
—
—
34
40
35
165
50
50
96
100
64
2.1
4.8
—
—
36
45
38
169
50
50
98
100
67
FLA
—
Full Load Amps
HACR —
Heating, Air Conditioning and Refrigeration
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps
MOCP —
Maximum Overcurrent Protection
NEC
—
National Electrical Code
RLA
—
Rated Load Amps
50
HJ
Q
Summary of Contents for WEATHERMASTER 50HJQ016
Page 19: ...19 Base unit dimensions 50TFQ004 007 50TFQ ...
Page 20: ...20 Base unit dimensions 50TFQ008 012 50TFQ ...
Page 84: ...84 Base unit dimensions 50HJQ004 007 50HJQ ...
Page 85: ...85 Base unit dimensions 50HJQ008 012 50HJQ ...
Page 141: ...141 Typical wiring schematics 50HJQ 50HJQ016 460 v shown 50HJQ ...