NOTE:

An HP temperature sensor must be used with a heat pump

application using electric strip heat. This is necessary in case the
DTO is set to the Off position.

Timeguard

The WeatherMaker Two-Zone provides equipment protection with
an internal 5-minute timeguard delay. This delay is present upon
initial power up. There is also a 5-minute timeguard delay for all

cooling (Y1) and heat pump modes. The time guard can be cleared
by using the comprotec override feature. Second-stage (Y2) and
(W2) will have a 5-minute delay between stages and also can be
cleared using the comprotec override feature.

Maximum Cycle Rate

The WeatherMaker Two-Zone will allow a maximum of 4
equipment cycles per hr or 1 every 15 minutes when a heating or
cooling mode is activated. When a demand exists, and internal

Fig. 13—Electronic Non-Programmable Thermostat Wiring Diagrams

A97294

W

/

W1

C

Y

/

Y2

R

24 VAC HOT

TWO-ZONE BOARD
THERMOSTAT
INPUT

24 VAC COMM

HEAT STAGE 1

COOL STAGE 2

FAN

HEAT STAGE 2

COOL STAGE 1

N/A

TROUBLE

OUTDOOR
SENSOR
CONNECTION

TWO-STAGE HEAT,
TWO-STAGE COOL

SEE NOTES 1, 2, AND 3

G

O

/

W2

Y1

C

R

W1

Y2

G

W2

Y1

B

L

S1

S2

W

/

W1

C

Y

/

Y2

R

24 VAC HOT

NON-PROGRAMMABLE

ELECTRONIC

THERMOSTAT

MODEL AC

NON-PROGRAMMABLE

ELECTRONIC

THERMOSTAT

MODEL HP

TWO-ZONE BOARD
THERMOSTAT
INPUT

24 VAC COMM

HEAT STAGE 1

COOL STAGE 1

FAN

SINGLE-STAGE HEAT,

SINGLE-STAGE COOL

SEE NOTES 1 AND 3

G

C

R

W1

Y1

G

W2

Y2

NON-PROGRAMMABLE

ELECTRONIC

THERMOSTAT

MODEL 2S

*

*

W

/

W1

C

Y

/

Y2

R

24 VAC HOT

TWO-ZONE BOARD
THERMOSTAT
INPUT

24 VAC COMM

HEAT STAGE 1

COOL STAGE 1

FAN

HEAT STAGE 2

N/A

N/A

N/A

OUTDOOR
SENSOR
CONNECTION

TWO-STAGE HEAT,
SINGLE-STAGE COOL

SEE NOTES 1, 2, AND 3

G

O

/

W2

Y1

C

R

W1

Y1

G

Y2

W2

B

L

S1

S2

*

WIRING DIAGRAM NOTES:

* Hook up G on zone 1 thermostat only.
Cut R19 jumper on thermostat.
Disable timeguard and cycle protection in thermostat by setting
it to ZONE mode.  Refer to thermostat Installation Instructions for
details on how to do this.

1.
2.
3.

7

Summary of Contents for WeatherMaker Two-Zone

Page 1: ...F and 150 F 2 Use vibration isolators flex connectors on zone dampers and ductwork to minimize noise 3 Place dampers away from areas that may be noise sensitive 4 TXV is required in air conditioning...

Page 2: ...mark on the end of the damper shaft represents the position of the damper blade NOTE Insulate damper using 1 1 2 in insulation check local codes In areas where excessive condensing may occur carefully...

Page 3: ...NOTE All zone dampers and ductwork must be properly sup ported according to local codes or SMACNA standards RECTANGULAR FIBROUS GLASS DUCTWORK 1 Insert 1 end of zone damper into 1 end of fibrous glas...

Page 4: ...e thermostat demand warrants Turn off heating or cooling equipment when all zones are satisfied Open all zone dampers when equipment is turned off after 90 sec delay This is the basic sequence of oper...

Page 5: ...ortant that this tempera ture is properly set For gas or oil furnaces the temperature limit will be in the higher temperature range For heat pumps the temperature setting should always be in the lower...

Page 6: ...4 F A E C K J I H L M N 2 3 1 ZONE 1 I O CENTER CONNECTIONS G G Y2 Y2 Y1 Y1 R R W1 W1 W2 W2 C C THERMOSTAT SUBBASE CONNECTIONS ONLY HOOKUP C WHEN SUPPLIED BY THERMOSTAT HOOKUP WHEN USING APPLICABLE TW...

Page 7: ...C Y Y2 R 24 VAC HOT TWO ZONE BOARD THERMOSTAT INPUT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FAN HEAT STAGE 2 COOL STAGE 1 N A TROUBLE OUTDOOR SENSOR CONNECTION TWO STAGE HEAT TWO STAGE COOL SEE NOTES 1...

Page 8: ...A TROUBLE OUTDOOR SENSOR CONNECTION TWO STAGE HEAT TWO STAGE COOL SEE NOTES 1 2 AND 3 O W2 B C G Y1 W1 Y2 R C L S1 S2 W2 W W1 G Y Y2 O W2 Y1 W2 R 24 VAC HOT TWO ZONE BOARD THERMOSTAT INPUT FAN HEAT ST...

Page 9: ...proper air temperatures DTO A Damper Fuse Protects damper from electrical dam age 3 Amp B High Heating Temperature Trip Limit Setting When DTO is On temperature is sensed by duct temperature sensor Wh...

Page 10: ...2 times and Red flashes 1 time HP temperature sensor error Second stage heat limit exceeded Wait until HP temperature cools below ex ceeded temperature trip Fixed at 105 F Green flashes 2 times and R...

Page 11: ...391 124 3469 1 288 167 1480 0 645 39 26 686 3 637 82 8776 2 337 126 3340 1 252 169 1431 0 626 41 25 396 3 587 84 8407 2 284 127 3217 1 217 171 1385 0 608 43 24 171 3 537 86 8056 2 231 129 3099 1 183 1...

Page 12: ...Y C W R G Y C RH G W2 W1 Y1 Y2 O B RC TWO ZONE SYSTEM Fig 18 FK4C Fan Coil With Single Speed Air Conditioner A97299 SINGLE SPEED AIR CONDITIONER FK4C FAN COIL C Y G W2 Y Y2 C R Y1 O RH G W2 W1 Y1 Y2...

Page 13: ...RH G W2 W1 Y1 Y2 O B RC TWO ZONE SYSTEM See note 2 Fig 22 FK4C Fan Coil With 2 Speed Air Conditioner A97303 RH G W2 W1 Y1 Y2 O B RC 2 SPEED AIR CONDITIONER FK4C FAN COIL TWO ZONE SYSTEM R G R C W1 W2...

Page 14: ...T C Y 2 1 3 OUTDOOR THERMOSTAT KHAOT0301FST See notes 4 5 6 and 7 KHAIC0101AAA Fig 24 Two Stage or Variable Speed Furnace With Single Speed Heat Pump A97305 2 STAGE OR VARIABLE SPEED FURNACE TWO ZONE...

Page 15: ...W3 C R Y Y2 O L E Y1 C W2 Y O RH G W2 W1 Y1 Y2 O B RC See notes 1 and 3 Fig 28 Two Stage or Variable Speed Furnace With 2 Speed Heat Pump A97309 2 SPEED HEAT PUMP 2 STAGE OR VARIABLE SPEED FURNACE C...

Page 16: ...rmostat AUTO CHANGEOVER mode with dual fuel applications keep both thermostats in same mode heating or cooling 7 Configure Two Zone Control board jumpers for J1 T stat Fnc J3 Equipmt HP J4 Fnc Ht w fa...

Reviews: