background image

Step 2—Wiring

To prevent personal injury or possible equipment damage,
disconnect the power supply before routing wire.

All wiring must comply with local, state, and national codes.

NOTE:

Use No. 18 AWG color-coded, insulated (35°C min)

wire. If thermostats are to be located more than 100 ft from the
WeatherMaker Two-Zone Center as measured along the control
voltage wires, use 16 AWG colored-coded wires to avoid exces-
sive voltage drop. All wiring is run back to the WeatherMaker
Two-Zone Center.

Step 3—Install WeatherMaker Two-Zone

NOTE:

WeatherMaker Two-Zone is approved for indoor use

only and should never be installed with any of its components
exposed to the elements. Do not mount WeatherMaker Two-Zone
Center where it will be accessible to children. Do not locate the
center in areas of the home that are noise sensitive since relays are
energized and de-energized during operation and may be an
annoyance. Install WeatherMaker Two-Zone in an area with a
temperature range between 32°F and 150°F.

Install WeatherMaker Two-Zone center in a vertical position.
Locate in an area that is easily accessible in case servicing should
be required.

To prevent possible damage to the WeatherMaker Two-Zone
Center, do not mount on plenum, ductwork, or flush against
furnace.

Step 4—Install Zone Dampers

IMPORTANT:

If conditions exist for possible condensing, the

motor must be positioned for adequate draining. (See Fig. 2.)

NOTE:

If a multi-damper enabler is used to link dampers

together, then add 5va per damper to the transformer power supply
rating. Reference multi-damper enabler Installation Instructions.

Zone dampers may be installed in any direction.

Install dampers so the actuator is visible for inspection and
accessible in the event it would ever need service. The black mark
on the end of the damper shaft represents the position of the
damper blade.

NOTE:

Insulate damper using 1-1/2 in. insulation (check local

codes). In areas where excessive condensing may occur, carefully

insulate over the actuator assembly. Make sure insulation does not
interfere with operation of actuator.

Before insulating the ductwork, check for proper damper opera-
tion. Apply 24vac between COM and OPN to open the damper and
COM and CLS to close the damper. (See Fig. 3.) The damper will
modulate counter-clockwise to open and clockwise to close.

If in an emergency it becomes necessary to force a damper open
manually, press in red quick blade release button with 1 hand and
turn mounting hub to reposition the damper shaft. Release button
to hold damper shaft in the new position.

To avoid noise and vibration, do not hard mount dampers to any
solid structure such as joists.

ROUND METAL DUCTWORK

IMPORTANT:

If application exists with all metal ductwork

without insulation, flex connectors should be used on each end of
the zone dampers to avoid noise and vibration.

1. Crimp end of branch duct.

2. Slip end of flex connector over zone damper and use self-

tapping sheet metal screw to secure. (See Fig. 4.)

3. Properly seal joint using duct tape, mastic, or other approved

method. Do not allow mastic to come in contact with actuator.

4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check

your local codes.) (See Fig. 5.)

NOTE:

All zone dampers and ductwork must be properly sup-

ported according to local codes or SMACNA standards.

RECTANGULAR METAL DUCTWORK

1. Make connections using S-lock and drives. (See Fig. 6.)

Fig. 2—Damper Motor Positioning

A95128

DAMPER

MOUNTING
BRACKET

ACTUATOR

Fig. 3—Damper 24-vac Connections

A95096

90

45

0

CLS

COM

OPN

ACTUATOR

HOUSING

MOUNTING
BRACKET

QUICK BLADE

RELEASE

BUTTON

(RED)

FIELD

INSTALLED

POWER WIRING

ANGULAR
ROTATION
STOPS 

POSITION
INDICATOR

MOUNTING

HUB

AIRFLOW

AIRFLOW

Fig. 4—Round Metal Ductwork

A95129

SUPPLY

FLEX

CONNECTOR

ZONE DAMPER

2

Summary of Contents for WeatherMaker Two-Zone

Page 1: ...F and 150 F 2 Use vibration isolators flex connectors on zone dampers and ductwork to minimize noise 3 Place dampers away from areas that may be noise sensitive 4 TXV is required in air conditioning...

Page 2: ...mark on the end of the damper shaft represents the position of the damper blade NOTE Insulate damper using 1 1 2 in insulation check local codes In areas where excessive condensing may occur carefully...

Page 3: ...NOTE All zone dampers and ductwork must be properly sup ported according to local codes or SMACNA standards RECTANGULAR FIBROUS GLASS DUCTWORK 1 Insert 1 end of zone damper into 1 end of fibrous glas...

Page 4: ...e thermostat demand warrants Turn off heating or cooling equipment when all zones are satisfied Open all zone dampers when equipment is turned off after 90 sec delay This is the basic sequence of oper...

Page 5: ...ortant that this tempera ture is properly set For gas or oil furnaces the temperature limit will be in the higher temperature range For heat pumps the temperature setting should always be in the lower...

Page 6: ...4 F A E C K J I H L M N 2 3 1 ZONE 1 I O CENTER CONNECTIONS G G Y2 Y2 Y1 Y1 R R W1 W1 W2 W2 C C THERMOSTAT SUBBASE CONNECTIONS ONLY HOOKUP C WHEN SUPPLIED BY THERMOSTAT HOOKUP WHEN USING APPLICABLE TW...

Page 7: ...C Y Y2 R 24 VAC HOT TWO ZONE BOARD THERMOSTAT INPUT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FAN HEAT STAGE 2 COOL STAGE 1 N A TROUBLE OUTDOOR SENSOR CONNECTION TWO STAGE HEAT TWO STAGE COOL SEE NOTES 1...

Page 8: ...A TROUBLE OUTDOOR SENSOR CONNECTION TWO STAGE HEAT TWO STAGE COOL SEE NOTES 1 2 AND 3 O W2 B C G Y1 W1 Y2 R C L S1 S2 W2 W W1 G Y Y2 O W2 Y1 W2 R 24 VAC HOT TWO ZONE BOARD THERMOSTAT INPUT FAN HEAT ST...

Page 9: ...proper air temperatures DTO A Damper Fuse Protects damper from electrical dam age 3 Amp B High Heating Temperature Trip Limit Setting When DTO is On temperature is sensed by duct temperature sensor Wh...

Page 10: ...2 times and Red flashes 1 time HP temperature sensor error Second stage heat limit exceeded Wait until HP temperature cools below ex ceeded temperature trip Fixed at 105 F Green flashes 2 times and R...

Page 11: ...391 124 3469 1 288 167 1480 0 645 39 26 686 3 637 82 8776 2 337 126 3340 1 252 169 1431 0 626 41 25 396 3 587 84 8407 2 284 127 3217 1 217 171 1385 0 608 43 24 171 3 537 86 8056 2 231 129 3099 1 183 1...

Page 12: ...Y C W R G Y C RH G W2 W1 Y1 Y2 O B RC TWO ZONE SYSTEM Fig 18 FK4C Fan Coil With Single Speed Air Conditioner A97299 SINGLE SPEED AIR CONDITIONER FK4C FAN COIL C Y G W2 Y Y2 C R Y1 O RH G W2 W1 Y1 Y2...

Page 13: ...RH G W2 W1 Y1 Y2 O B RC TWO ZONE SYSTEM See note 2 Fig 22 FK4C Fan Coil With 2 Speed Air Conditioner A97303 RH G W2 W1 Y1 Y2 O B RC 2 SPEED AIR CONDITIONER FK4C FAN COIL TWO ZONE SYSTEM R G R C W1 W2...

Page 14: ...T C Y 2 1 3 OUTDOOR THERMOSTAT KHAOT0301FST See notes 4 5 6 and 7 KHAIC0101AAA Fig 24 Two Stage or Variable Speed Furnace With Single Speed Heat Pump A97305 2 STAGE OR VARIABLE SPEED FURNACE TWO ZONE...

Page 15: ...W3 C R Y Y2 O L E Y1 C W2 Y O RH G W2 W1 Y1 Y2 O B RC See notes 1 and 3 Fig 28 Two Stage or Variable Speed Furnace With 2 Speed Heat Pump A97309 2 SPEED HEAT PUMP 2 STAGE OR VARIABLE SPEED FURNACE C...

Page 16: ...rmostat AUTO CHANGEOVER mode with dual fuel applications keep both thermostats in same mode heating or cooling 7 Configure Two Zone Control board jumpers for J1 T stat Fnc J3 Equipmt HP J4 Fnc Ht w fa...

Reviews: