background image

In automatic changeover, the zoning system works on a first come
first serve basis. If 1 zone is calling for heating and the other for
cooling, the zone which sent its demand to the I/O center first will
operate the equipment in that mode until that zone is satisfied.

Step 5—Duct Temperature Optimizer (DTO)
For Monitoring Leaving Air Temperature

As the WeatherMaker Two-Zone System operates through a
heating or cooling cycle, the zone demands will change. This
changes actual load that is applied to the HVAC equipment. If the
zone airflow decreases, the cooling equipment will tend to lower
supply-air temperatures which could tend to exceed the LAT trip
limits. Conversely, the heating equipment will tend to raise the
supply-air temperatures which could exceed high trip limits. In
cooling, when the LAT reaches the non-adjustable low tempera-
ture trip limit (50°F) the LAT algorithm begins operating, closed
dampers are initially opened 3 positions, then 1 position every 20
sec there after until full open. WeatherMaker Two-Zone will not
shut down second-stage cooling (if used); however, if temperature
continues to drop to 45°F, the zoning system will turn off both
stages of cooling. If the temperature improves, the system will stay
in the duct temperature optimizer mode until the LAT reaches
55°F or higher. At 55°F the LAT algorithm will reset and return
dampers to their original position. In the heating mode, Weather-
Maker Two-Zone will perform the same duct temperature optimi-
zation. The trip limits will be determined by the jumper setting.
(See Fig. 12.) This will continue until the LAT problem is
corrected.

This control helps WeatherMaker Two-Zone System cope with
installations where the air conditioning system may suffer from
poor ductwork, improperly sized heating or cooling equipment,
and/or improper settings of the barometric bypass damper. This
control is especially useful in retrofit applications where the size
and routing of the ductwork may not be entirely known or
satisfactory.

The duct temperature optimizer works by controlling how cold or
hot the air inside the supply-air duct gets by monitoring the
temperature of the air inside the supply-air system.

Whenever WeatherMaker Two-Zone is providing heating or cool-
ing, the zone within the home that is asking for conditioned air will
always have its damper fully open. The other zone in the system
may or may not have an open damper depending upon its
particular needs. If the ductwork is too small (or the air
conditioner/heater is too large), then the zone requiring condi-
tioned air may not be able to take enough air to allow your
equipment to operate properly. WeatherMaker Two-Zone will
detect this, and open up the closed damper allowing the equipment
to continue to operate.

The duct temperature optimizer may be disabled on the
control center. A 10k resistor can be installed in place of the
duct sensor at the terminal block. By disabling the duct
temperature optimizer, the LAT safety algorithm is removed
from the system.

It is highly recommended that you use this control option. The
heating LAT is adjustable for the duct sensor. In this Installation
Instruction, you will find the section showing an adjustment for the
heating LAT. (See Fig. 12.) It is very important that this tempera-
ture is properly set. For gas or oil furnaces, the temperature limit
will be in the higher temperature range. For heat pumps the
temperature setting should always be in the lower temperature
range.

If you encounter a situation where 1 zone seems to have poor
ductwork, then the WeatherMaker Two-Zone system is capable of
reverting back to a fully open, constant-volume system. If this
condition persists, it should always be looked upon as an indication
of a HVAC problem, not a WeatherMaker Two-Zone problem.

Step 6—Electronic Thermostat Connection with
WeatherMaker Two-Zone Control

Carrier electronic non-programmable and programmable thermo-
stats can be connected to the WeatherMaker Two-Zone. See
pre-sale literature for thermostat part numbers.

NOTE:

The zone control board is only capable of 2-stage heat

and 2-stage cool operation. Fig. 13 and 14 will reflect these
applications only. Review and understand the following items
before installing.

THERMOSTAT SETUP

1. Thermostat will not operate unless both R and C are connected

to zone module input.

2. If selected thermostat is a heat pump (HP) or 2-speed (2S)

model, convert thermostat to air conditioning operation. This
will assure that Y signals are generated for cooling, and W
signals are generated for heating from thermostat to zone
module input. The thermostat O/W2 output will now be the
second-stage heat call. If installation is a heat pump system,
the zone control board will provide proper output signal to
heat pump.

3. Select "Zoning" option on thermostat. This will disable the

Timeguard and 4-cycle per hr (cph) protection built into
thermostat. Let zone control board perform the Timeguard and
cycle protection. Refer to thermostat Installation Instruction
under Zoning for more detail.

4. The zone 1 thermostat is the only thermostat that can control

continuous fan operation with zoning. Connect G between
zone 1 thermostat and zone 1 input on zone control module.

5. Follow all safety and installation considerations outlined in the

thermostat Installation Instructions.

ZONE CONTROL BOARD SETUP

1. Configure zone control board jumper for Tstat (thermostat)

Fnc option only. Do not use Tstat HP option. When Tstat Fnc
is selected this will setup control inputs to recognize Y1 and
Y2 for first- and second-stage cooling, W1 and W2 for first-
and second-stage heating.

2. Configure zone control board for either Equipmt (equipment),

HP or Fnc. When a heat pump system is used, Equipmt HP
mode should be selected. The zone control board will provide
the proper output signal to the heat pump. When a gas/electric
furnace is used, Equipmt Fnc mode should be selected for
proper output signal.

3. Configure zone control board for either Fnc Ht, w/f (with fan),

or w/of (without fan). With Fan mode should be selected when
a heat pump is installed and fan is needed to come on
immediately with demand. Without Fan mode should be
selected when fan is controlled by gas/electric furnace.

4. Configure zone control board for either DTO On or Off. When

DTO On is selected (Factory default) and if a LAT trip occurs,
closed dampers will begin opening to try and keep equipment
running by maintaining proper air temperatures. However, if
LAT temperatures exceed their limits, equipment will start
staging down. When DTO Off is selected, equipment will
stage down. Closed dampers will not open on inial trip,
however if LAT temperatures exceed their limits, control will
lockout and damper will open.

5

Summary of Contents for WeatherMaker Two-Zone

Page 1: ...F and 150 F 2 Use vibration isolators flex connectors on zone dampers and ductwork to minimize noise 3 Place dampers away from areas that may be noise sensitive 4 TXV is required in air conditioning...

Page 2: ...mark on the end of the damper shaft represents the position of the damper blade NOTE Insulate damper using 1 1 2 in insulation check local codes In areas where excessive condensing may occur carefully...

Page 3: ...NOTE All zone dampers and ductwork must be properly sup ported according to local codes or SMACNA standards RECTANGULAR FIBROUS GLASS DUCTWORK 1 Insert 1 end of zone damper into 1 end of fibrous glas...

Page 4: ...e thermostat demand warrants Turn off heating or cooling equipment when all zones are satisfied Open all zone dampers when equipment is turned off after 90 sec delay This is the basic sequence of oper...

Page 5: ...ortant that this tempera ture is properly set For gas or oil furnaces the temperature limit will be in the higher temperature range For heat pumps the temperature setting should always be in the lower...

Page 6: ...4 F A E C K J I H L M N 2 3 1 ZONE 1 I O CENTER CONNECTIONS G G Y2 Y2 Y1 Y1 R R W1 W1 W2 W2 C C THERMOSTAT SUBBASE CONNECTIONS ONLY HOOKUP C WHEN SUPPLIED BY THERMOSTAT HOOKUP WHEN USING APPLICABLE TW...

Page 7: ...C Y Y2 R 24 VAC HOT TWO ZONE BOARD THERMOSTAT INPUT 24 VAC COMM HEAT STAGE 1 COOL STAGE 2 FAN HEAT STAGE 2 COOL STAGE 1 N A TROUBLE OUTDOOR SENSOR CONNECTION TWO STAGE HEAT TWO STAGE COOL SEE NOTES 1...

Page 8: ...A TROUBLE OUTDOOR SENSOR CONNECTION TWO STAGE HEAT TWO STAGE COOL SEE NOTES 1 2 AND 3 O W2 B C G Y1 W1 Y2 R C L S1 S2 W2 W W1 G Y Y2 O W2 Y1 W2 R 24 VAC HOT TWO ZONE BOARD THERMOSTAT INPUT FAN HEAT ST...

Page 9: ...proper air temperatures DTO A Damper Fuse Protects damper from electrical dam age 3 Amp B High Heating Temperature Trip Limit Setting When DTO is On temperature is sensed by duct temperature sensor Wh...

Page 10: ...2 times and Red flashes 1 time HP temperature sensor error Second stage heat limit exceeded Wait until HP temperature cools below ex ceeded temperature trip Fixed at 105 F Green flashes 2 times and R...

Page 11: ...391 124 3469 1 288 167 1480 0 645 39 26 686 3 637 82 8776 2 337 126 3340 1 252 169 1431 0 626 41 25 396 3 587 84 8407 2 284 127 3217 1 217 171 1385 0 608 43 24 171 3 537 86 8056 2 231 129 3099 1 183 1...

Page 12: ...Y C W R G Y C RH G W2 W1 Y1 Y2 O B RC TWO ZONE SYSTEM Fig 18 FK4C Fan Coil With Single Speed Air Conditioner A97299 SINGLE SPEED AIR CONDITIONER FK4C FAN COIL C Y G W2 Y Y2 C R Y1 O RH G W2 W1 Y1 Y2...

Page 13: ...RH G W2 W1 Y1 Y2 O B RC TWO ZONE SYSTEM See note 2 Fig 22 FK4C Fan Coil With 2 Speed Air Conditioner A97303 RH G W2 W1 Y1 Y2 O B RC 2 SPEED AIR CONDITIONER FK4C FAN COIL TWO ZONE SYSTEM R G R C W1 W2...

Page 14: ...T C Y 2 1 3 OUTDOOR THERMOSTAT KHAOT0301FST See notes 4 5 6 and 7 KHAIC0101AAA Fig 24 Two Stage or Variable Speed Furnace With Single Speed Heat Pump A97305 2 STAGE OR VARIABLE SPEED FURNACE TWO ZONE...

Page 15: ...W3 C R Y Y2 O L E Y1 C W2 Y O RH G W2 W1 Y1 Y2 O B RC See notes 1 and 3 Fig 28 Two Stage or Variable Speed Furnace With 2 Speed Heat Pump A97309 2 SPEED HEAT PUMP 2 STAGE OR VARIABLE SPEED FURNACE C...

Page 16: ...rmostat AUTO CHANGEOVER mode with dual fuel applications keep both thermostats in same mode heating or cooling 7 Configure Two Zone Control board jumpers for J1 T stat Fnc J3 Equipmt HP J4 Fnc Ht w fa...

Reviews: