13
unit disconnect. On a unit without a unit--mounted
disconnect, connect the source leads to compressor
contactor C and indoor fan terminal block (IFTB) pressure
lugs with unit field power leads.
Refer to Fig. 28 for power transformer connections and
the discussion on connecting the convenience outlet on
page 20.
Field power wires are connected to the unit at line--side
pressure lugs on compressor contactor C and indoor fan
terminal block (IFTB) (see wiring diagram label for
control
box
component
arrangement)
or
at
factory--installed option non--fused disconnect switch or
HACR. Max wire size is #2 ga AWG (copper only) per
pole on contactors. #2 ga AWG per pole on optional
disconnect or HACR and 4/0 AWG per pole on terminal
or fuse block on units with single point box. See Fig. 16
and unit label diagram for field power wiring connections.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in
intermittent operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and 50LC unit. Use only copper wire.
(See Fig. 15.)
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
A93033
Fig. 15 -- Disconnect Switch and Unit
Units Without Single Point Box, Disconnect or HACR Option
Units With Disconnect or HACR Option
L1
L2
L3
2
4
6
1
5
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
3
Equip GR Lug
Ground
(GR)
Units With Electric Heat Option with Single Point Box
and Without Disconnect or HACR Option
L1
L2
L3
Single Point Box
Factory
Wiring
Equip GR
Lug
Ground (GR)
Terminal Block
— OR —
L1
L2
L3
Single Point Box
Factory
Wiring
Equip GR
Lug
Ground (GR)
Fuse/Terminal Block
Fuse
Fuse
Fuse
Disconnect
per
NEC
11
12
13
L1
L2
L3
C
208/230-3-60
460-3-60
575-3-60
Ground
(GR)
Equip
GR Lug
13262
Fig. 16 -- Power Wiring Connections
Summary of Contents for WeatherExpert 50LC
Page 4: ...4 a50 9584 Fig 2 Unit Dimensional Drawing ...
Page 5: ...5 a50 9585 Fig 2 Unit Dimensional Drawing cont ...
Page 14: ...14 a50 9586 Fig 17 50LC 07 Electro mechanical Control Wiring Diagram ...
Page 15: ...15 a50 9592 Fig 18 50LC 07 RTU Open Control Wiring Diagram ...
Page 16: ...16 a50 9587 Fig 19 50LC 07 SystemVut Control Wiring Diagram ...