29
The W7220 control also includes a new capability that
will adjust the damper control points during DCV or
minimum ventilation operation as the indoor fan speed is
changed. This control function ensures that required space
ventilation airflow quantities are maintained during
reduced fan speed operation.
Additional
control
capabilities
include
automatic
detection of new sensors and detection of sensor failure or
loss of communication.
The W7220 control module includes an integral user
interface with keypad and LCD display that permits direct
input of setpoint values and configurations and display of
status and alarms.
The W7220 controller is located in the RTU base unit’s
Control Box. See the Installation Instructions for this base
unit for the location of the Control Box access panel.
User Interface —
The user interface consists of a 2--line LCD display and a
4--button keypad on the front of the economizer controller.
2 LINE
LCD
MENU UP
(EXIT)
BUTTON
SCROLL
UP/DOWN
BUTTONS
SELECT
(ENTER)
BUTTON
C14206
Fig. 44 -- W7220 Controller
Keypad
The four navigation buttons (see Fig. 44) are used to scroll
through the menus and menu items, select menu items,
and to change parameter and configuration settings.
Using the Keypad with Menus
To use the keypad when working with menus:
S
Press the
(Up arrow) button to move to the previous
menu.
S
Press the
(Down arrow) button to move to the next
menu.
S
Press the
(Enter) button to display the first item in
the currently displayed menu.
S
Press the
(Menu Up/Exit) button to exit a menu’s
item and return to the list of menus.
The Menus in display order are:
S
STATUS
S
SETPOINTS
S
SYSTEM SETUP
S
ADVANCED SETUP
S
CHECKOUT
S
ALARMS
Using the Keypad with Settings and Parameters
To use the keypad when working with Setpoints, System
and Advanced Settings, Checkout tests and Alarms:
1. Navigate to the desired menu.
2. Press the
(Enter) button to display the first item in
the currently displayed menu.
3. Use the
and
buttons to scroll to the desired pa-
rameter.
4. Press the
(Enter) button to display the value of the
currently displayed item.
5. Press the
button to increase (change) the displayed
parameter value.
6. Press the
button to decrease (change) the displayed
parameter value.
NOTE
: When values are displayed, pressing and
holding the
or
button causes the
display to automatically increment.
7. Press the
(Enter) button to accept the displayed
value and store it in nonvolatile RAM.
8. “CHANGE STORED” displays.
9. Press the
(Enter) button to return to the current
menu parameter.
10. Press the
(Menu Up/Exit) button to return to the
previous menu.
Menu Structure
IMPORTANT
: Table 5 illustrates the complete hierarchy.
Your menu parameters may be different depending on
your configuration. For example if you do not have a
DCV (CO
2
) sensor, then none of the DCV parameters
appear.
The menu hierarchy has been modified to reflect controller
configuration for 2--speed indoor fan application in the
Staged Air Volume option.
NOTE
: Some parameters in the menus use the letters MA
or MAT, indicating a mixed air temperature sensor
location before the cooling coil. This unit application has
the control sensor located after the cooling coil, in the fan
section, where it is designated as (Cooling) Supply Air
Temperature or SAT sensor.
Summary of Contents for WeatherExpert 50LC
Page 4: ...4 a50 9584 Fig 2 Unit Dimensional Drawing ...
Page 5: ...5 a50 9585 Fig 2 Unit Dimensional Drawing cont ...
Page 14: ...14 a50 9586 Fig 17 50LC 07 Electro mechanical Control Wiring Diagram ...
Page 15: ...15 a50 9592 Fig 18 50LC 07 RTU Open Control Wiring Diagram ...
Page 16: ...16 a50 9587 Fig 19 50LC 07 SystemVut Control Wiring Diagram ...