38
JBus
code
Alarm
code Description
Reset type
Action taken
Possible cause
VFD warning
104
35nnn
Circuit A Compressor VFD Warning
Automatic
No action (alert)
See section 9.6.4
105
36nnn
Circuit B Compressor VFD Warning
Automatic
No action (alert)
See section 9.6.4
106
38nnn
Circuit A Fan VFD 1 Warning
Automatic (China only);
Manual, if Danfoss drive
alarm 13 or 204 is triggered
No action (alert)
See section 9.6.5
107
39nnn
Circuit A Fan VFD 2 Warning
As above
No action (alert)
See section 9.6.5
108
40nnn
Circuit A Fan VFD 3 Warning
Not applicable
-
-
109
41nnn
Circuit B Fan VFD 1 Warning
Automatic (China only);
Manual, if Danfoss drive
alarm 13 or 204 is triggered
No action (alert)
See section 9.6.5
110
42nnn
Circuit B Fan VFD 2 Warning
As above
No action (alert)
See section 9.6.5
111
43nnn
Circuit B Fan VFD 3 Warning
Not applicable
-
-
Compressor failure
114
1101
Motor Temperature too high
Manual
Circuit A shuts down
Motor/wiring fault
115
2101
Motor Temperature too high
Manual
Circuit B shuts down
As above
116
1103
High Pressure Switch
Manual
Circuit A shuts down
Coil fouled, lack of
condenser flow,
condenser valve blocked,
fan circuit fault, high
entering air or condenser
water temperature
117
2103
High Pressure Switch
Manual
Circuit B shuts down
As above
Software failure
118
55001 Database module failure
Automatic
No action (alert); it is highly
recommended to power
cycle the Display panel
Software problem. Contact
Carrier Service
119
56001 Lenscan module failure
Automatic
As above
As above
EXV failure
120
57020 Main EXV stepper Motor failure – cir A
Manual
Circuit A shuts down
EXV motor fault
121
57021 Main EXV stepper Motor failure – cir B
Manual
Circuit B shuts down
EXV motor fault
122
57023 Main Eco stepper Motor failure – cir A
Manual
Circuit A shuts down
EXV motor fault
123
57024 Main Eco stepper Motor failure – cir B
Manual
Circuit B shuts down
EXV motor fault
9.6.2 -
Master/Slave configuration alarms
Alarm code
Description
9001
Lag pump control is selected while pump configuration is missing
9002
Master unit and Slave unit have the same address
9003
No Slave unit configured
9004
Slave lag pump is selected while slave pump configuration is missing
9005
Master unit and Slave unit should have the same water control type (control based on EWT)
9006
Master unit and Slave unit have the same water control type (control based on LWT)
9007
Master lag pump control is configured while the slave lag pump control is not configured
9008
Master lag pump control is not configured while the slave lag pump control is configured
9009
Slave unit is not in Network mode
9010
Slave unit failure due to a detected alarm
9011
Master unit is not in Network mode
9012
Communication between Master unit and Slave lost
9013
Master/Slave units heat/cool selection conflict
9014
Master and Slave parallel/series selection conflict
9015
Master unit has EWT option configured in conflict with chiller in series setting
9016
Slave unit has EWT option configured in conflict with chiller in series setting
9.6.3 - Service maintenance alarms
Alarm code
Description
13001
001: Oil filter
13002
002: Liquid line filter
13003
003: Check and replace fuses
13004
004: Check and clean the water filter
13005
005: Periodic leakage check
13006
006: Routine service visit as per IOM level 2
13007
007: Oil analysis
13008
008: Glycol level check
13009
009: Check the anti-vibration mounts