22
Energy Monitoring Menu – ENERGY
No. Name
Status
Unit
Displayed text*
Description
1
coolPowT
-
kW
Cooling Power Total
Cooling power (circuit A + circuit B)
2
powIn
-
kW
Electrical Power input
Electrical power input of compressors and fans
(estimated if EC fans are selected)
3
eer
-
-
Energy Efficiency
Energy efficiency (circuit A + circuit B)
4
5
energOut
-
kWh
Cooling Energy output
Cooling energy output
6
energyIn
-
kWh
Electrical Energy input
Electrical energy input of compressors and fans
(estimated if EC fans are selected)
7
energEER
-
-
Integrated EER
Integrated EER (Energy Efficiency Ratio)
8
reset_en
no/yes
-
Reset energy counter
Used to reset energy counter
9
reset_da
-
-
Last Reset Date
Last reset date
10
reset_ti
-
-
Last Reset time
Last reset time
11
12
powPmp
-
kW
Pump Elec Power Input
Pump electric power input
13
energyP
-
kWh
Pump Elec Energy Input
Pump electric energy input
14
resetpmp
no/yes
-
Reset pump energy
Used to reset pump energy counter
15
pmp_date
-
-
Pump Last Reset Date
Last reset date (pump)
16
pmp_time
-
-
Pump Last Reset time
Last reset time (pump)
*Depends on the selected language (English by default).
Setpoint Menu – SETPOINT
No. Name
Status
Default
Unit
Displayed text*
Description
1
csp1
-28.9 to 26
6.7
°C
Cooling Setpoint 1
Cooling setpoint 1 (used during occupied periods)
2
csp2
-28.9 to 26
6.7
°C
Cooling Setpoint 2
Cooling setpoint 2 (used during unoccupied periods)
3
ice_sp
-28.9 to 26
6.7
°C
Cooling Ice Setpoint
Ice storage setpoint
4
cramp_sp
0.1 to 11.1
0.5
K
Cooling Ramp Loading Cooling ramp loading setpoint
(rate at which the water temperature may change
within one minute in Cooling mode)
5
hsp1
26.7 to 63
37.8
°C
Heating Setpoint 1
Not applicable to this unit
6
hsp2
26.7 to 63
37.8
°C
Heating Setpoint 2
Not applicable to this unit
7
hramp_sp
0.1 to 11.1
0.5
K
Heating Ramp Loading Not applicable to this unit
8
cauto_sp
3.9 to 50
23.9
°C
Cool Changeover Setpt Not applicable to this unit
9
hauto_sp
0 to 46
17.8
°C
Heat Changeover Setpt Not applicable to this unit
10
vpmpdtsp
1 to 29
5
K
Varipump Delta Temp
Stp
Variable speed pump, water flow based on
delta T control
11
vpmpdpsp
50 to 620
200
kPa
Varipump Pressure Stp Variable speed pump pressure setpoint
12
lim_sp1
0 to 100
100
%
Switch Limit Setpoint 1 Demand limit setpoint 1
13
lim_sp2
0 to 100
100
%
Switch Limit Setpoint 2 Demand limit setpoint 2
14
lim_sp3
0 to 100
100
%
Switch Limit Setpoint 3 Demand limit setpoint 3
*Depends on the selected language (English by default).