background image

1

INTRODUCTION

About this Manual  –

 This manual provides instructions

for using the Touch Pilot as a Carrier communicating net-
work (CCN) user interface.

NOTE:  All instructions in this manual assume that the Touch
Pilot is physically connected to the CCN Bus (versus di-
rectly to a chiller) and that the Display is in Network mode
operating as a CCN user interface, as specified using the
Main Menu's Setup option.

SAFETY CONSIDERATIONS

Air-conditioning equipment will provide safe and reliable
service when operated within design specifications. The
equipment should be operated and serviced only by autho-
rized personnel who have a thorough knowledge of system
operation, safety devices and emergency procedures.

Good judgement should be used in applying any
manufacturer’s instructions to avoid injury to personnel or
damage to equipment and property.

GENERAL

The Touch Pilot (33CNTPILOT) is a user interface for the
Carrier communicating network and serves as a user inter-
face and configuration tool for the AQUAFORCE

TM

 and other

chillers, a Carrier 3V

TM

 zoning system, linkage-compatible

air source, and all Carrier communicating devices.

INSTALLATION

Location

 — The Touch Pilot is typically located in the

facility manager's office. It should be located where it is
easily accessible and visible to the end user.

Although the Display is approved for outdoor temperatures
under most conditions, it should never be installed with
any of its components directly exposed to the elements.
The Display must be installed in an area where the tempera-
ture remains between  -4 to 158 F (-20 to 70 C), and in a non-
condensing environment where the humidity is limited to
10-85% at or below 104 F (40 C), and 10-76% from 104 F to
158 F (40 to 70 C).

Power Transformer Wiring 

— An individual, field-sup-

plied, 24 Vac power transformer is recommended for each
Touch Pilot. Transformers must be UL Class 2 rated. Stan-
dard applications require a 24 Vac transformer, rated at 20
VA typical. All transformer secondaries are required to be
grounded. Use only stranded copper conductors for all wir-
ing to the Display.
Wiring connections must be made in accordance with NEC
(National Electrical Code) and local codes. Ground one side
of the transformer secondary at the transformer location.
Connect the system ground of the transformer to the Dis-
play terminal J1-3 (EARTH). Connect the 24 Vac– side of
the transformer to the Display terminal J1-2 (24 Vac–). Con-
nect the 24 Vac+ live side of the transformer to the Display
terminal J1-1 (24 Vac+). See Figure 2 on page 3. The power
supply is 24 Vac at 60 Hz ± 15%, 10 VA minimum.
NOTE:  Do not run sensor or communication wiring in the
same conduit with line-voltage wiring. Do not run 24 Vac
wiring in the same multi-conductor cable used for sensors

or communications.

Perform the following steps to connect the power trans-
former:
1. Install the field-supplied transformer in an electrical en-

closure that conforms to NEC and local codes.

2. Connect 24 Vac from the transformer as shown in the

wiring diagram (Figure 2). Be sure to observe polarity
when connecting the transformer power. The grounded
terminal must be connected to the transformer ground
terminal as described previously under Power Transformer
Wiring.
If the Display is powered with the same transformer as
the other devices, be sure that polarity is maintained and
that adequate power is available for all devices. Never
power half-wave and full-wave devices on the same trans-
former or damage may occur to one or both devices.

Carrier Network Communication Bus Wiring

 —

The Touch Pilot connects to the bus in a daisy chain ar-
rangement. See Figure 1 on page 3. It may be installed on a
primary Carrier communication bus or on a local bus wired
to an equipment controller’s LEN (Local Equipment Net-
work) port.

At any baud (9600, 19200, 38400 baud), the number of
controllers is limited to the application requirements. Bus
length may not exceed 4000 ft, with no more than 60 total
devices on any 1000-ft section. Optically isolated RS-485
repeaters are 

required every 1000 ft.

COMMUNICATION BUS WIRE SPECIFICATIONS —
The communication bus wiring is field-supplied and field
installed. It consists of shielded three-conductor cable with
drain (ground) wire. The cable selected must be identical to
the communication bus wire used for the entire network.
See Table 1 for recommended cable.

Table 1 — Recommended Cables

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

NOTE: Conductors and drain wire must be at least 20 AWG (American Wire Gage), stranded,
and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon,
or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/
nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C
is required.

CONNECTION TO THE COMMUNICATION BUS
1. Strip the ends of the red, white, and black conductors of

the communication bus cable.

2. Connect one end of the communication bus cable to the

communication port labeled CCN or COMM1 of the other
devices on the communication bus. See Figure 1. For net-
work applications, the CCN or COMM1 connector is typi-
cally the network bus connector.

Summary of Contents for Touch Pilot 33CNTPILOT

Page 1: ... 2 Decorative Bezel 2 Chiller Display Mounting 2 Operation 4 Power Up Display 4 Default Device Designation 4 Default Group Designation 4 Group Display Screen 4 To Remove a Point from a Group Display 5 To Add a Point to a Group Display 5 Navigation and Operation Pushbuttons 5 BACK 5 HOME 5 MAIN MENU 5 PREVIOUS 5 NEXT 5 OK 5 NO 5 CANCEL 5 CLEAR DATA 5 RESET DATA 5 ADD 5 REMOVE 5 INC DEC 5 SCROLL UP ...

Page 2: ...ii ...

Page 3: ... 24 Vac See Figure 2 on page 3 The power supply is 24 Vac at 60 Hz 15 10 VA minimum NOTE Do not run sensor or communication wiring in the same conduit with line voltage wiring Do not run 24 Vac wiring in the same multi conductor cable used for sensors or communications Perform the following steps to connect the power trans former 1 Install the field supplied transformer in an electrical en closure...

Page 4: ...e Figure 4 on page 3 The assembly will mount directly to the wall requiring only a small hole in the wall allowing the wiring connection to pass through Use four 8 x 1 5 in Phillips panhead screws and four wall anchors to fasten the Display to the wall DECORATIVE BEZEL A decorative bezel is supplied Af ter mounting and wiring the Display snap the decorative bezel on the Display to cover the mounti...

Page 5: ...Wiring 1 2 3 6 5 4 1 2 3 COMM GND 1000 FT MAXIMUM DRAIN WIRE TYP BLK TYP WHT TYP RED TYP BYPASS CONTROLLER ZONE CONTROLLER SYSTEM PILOT ZONE CONTROLLER BRIDGE RECOMMENDED 1 2 3 1 2 3 CCN CCN CCN CCN CHILLER DISPLAY Figure 3 Touch Pilot Bezel Figure 4 Touch Pilot Surface Mounting ...

Page 6: ...FORCETM chiller contains all 8 group displays Going forward more Carrier equipment will support this group functionality Following installation and initial power up the installer should Login and then select the Setup option from the Main Menu to access the display s various setup and con figuration functions Refer to Login and Setup which ap pear in the Main Menu section of this manual Figure 5 E...

Page 7: ...AIN MENU Displays the Main Menu screen A description of all Main Menu options can be found in the Main Menu section of this manual PREVIOUS In a group of sequential screens of the same type moves to the next earlier screen in the group NEXT In a group of sequential screens of the same type advances to the next screen in the group OK Agrees with or says yes to a prompt and performs the appropriate ...

Page 8: ...owing this Main Menu section ATTACH Pressing the Main Menu s button will allow you to display the Attach list where you can select an existing device or add a new device and then establish communication with the selected device The At tach list consists of device name bus and element num bers The first entry in the Attach list surrounded by two is referred to as the Default device It will be the d...

Page 9: ...able screen If the device has multiple tables of that type the Display will show a list of tables from which you can select the one you wish to access As you make changes to values in these tables the new values will be displayed On pressing a Navigation pushbutton to exit the current screen a confirmation mes sage will be displayed Pressing will save and down load the new values to the attached d...

Page 10: ... designation CONFIGURATION TABLES Display operation is controlled by decisions entered in the the following configuration tables which are accessible from a Carrier front end such as the Network Service Tool or ComfortVIEW CtlrID Controller Identification Configuration Table USERCONF User Configuration Table NOTE You should always perform an Upload to obtain the latest configuration before making ...

Page 11: ...Default Value 0 Network Settings Alarm Acknowledger Use this decision to specify whether the Touch Pilot will act as the alarm acknowledger for its CCN There must be only one alarm acknowledger per CCN Therefore if another CCN device such as ComfortVIEW the Autodial Gateway or TeLINK is already set as the Alarm Acknowledger for the CCN then this deci sion should be set to No NOTE The Display must ...

Page 12: ... Value blank Disable START STOP control Equipment Start Stop This decision is used in conjunc tion with the Display s Start Stop button Enter the CCN variable name of the equipment point to which the Start Stop output point is connected If you press the button while in equipment mode the Display will first look at the equipment point s status in accordance with the variable name you entered in the...

Reviews: