decision set to Yes for broadcast acknowledgement to be

enabled.

Allowable Entries: 0 = No

1 = Yes

Default Value:

0

Equipment CCN Address  –
When in equipment mode (USERCONF Table's Network
Mode decision is set to Disable),  the Bus Number and
Element Number decisions are used to specify the CCN ad-
dress of the piece of equipment to which you wish to com-
municate. You must perform an Attach or cycle power for
changes to these decisions to take effect. These decisions
will be ignored when the Display is connected to the LEN
bus or in Network mode. In network mode, you specify the
bus and element number of the equipment to which you
wish to communicate using the Display's Attach function.
For additional information, see Attach in the Main Menu
section of this manual.

NOTE:  In Network mode, these decisions will be overwrit-
ten with the Default device address if it is changed through
the Attach process.

Bus Number – Use this decision to specify the Equipment
Controller bus number .

Allowable 

Entries:

0 through 239

Default Value:

0

Element Number  –  Use this decision to specify the Equip-
ment Controller element number .

Allowable 

Entries:

1 through 239

Default Value:

1

Control Variables
Use the next 4 decisions to specify the names of the CCN
equipment variables that will be used to implement the Start/
Stop Control and Alarm Indication functionality.

Equipment Status  – This decision is used in conjunction
with the Display's Start/Stop button. Enter the CCN variable
name of the equipment input point to which the on/off sta-
tus indicator is connected. This name can be obtained from
the CCN equipment's status display table. This decision will
be ignored when the Display is in network mode.

Allowable Entries: Up to 8 character CCN variable name

Valid characters include A to Z,
0 to 9, dash and underscore

Default Value:

blank = Disable START/STOP control

Equipment Start/Stop  – This decision is used in conjunc-
tion with the Display's Start/Stop button. Enter the CCN
variable name of the equipment point to which the Start/
Stop output point is connected. If you press the button
while in equipment mode, the Display will first look at the
equipment point's status (in accordance with the variable
name you entered in the Equipment Status decision above)
and then start or stop the equipment point that you specify
in this decision. This name can be obtained from the CCN

equipment's status display table. This decision will be ig-
nored when the Display is in network mode.

Allowable Entries: Up to 8 character CCN variable name

Valid characters include A to Z,
0 to 9, dash and underscore

Default Value:

blank = Disable START/STOP control

Alarm Status  – This decision is used in conjunction with
the Display's Alarm Indicator light. When in equipment
mode, the Display will read the value of the input point that
you specify in this decision and will turn the indicator light
on or off accordingly. Enter the CCN variable name of the
equipment input point to which the alarm status indicator is
connected. This name can be obtained from the attached
device's status display table. This decision will be ignored
when the Display is in network mode or attached to a

AquaForce

 chiller

.

Allowable Entries: Up to 8 character CCN variable name

Valid characters include A to Z,
0 to 9, dash and underscore

Default Value:

blank

Alarm Reset  – This decision is used in conjunction with
the Reset button on the Main Menu. When in equipment
mode, the Display will reset the alarm status equipment point
that you specify in this decision and will turn off the Alarm
Indicator light when the Reset button is pressed. This deci-
sion will be ignored when the Display is in network mode or
attached to an AquaForce chiller.

Allowable Entries: Up to 8 character CCN variable name

Valid characters include A to Z,
0 to 9, dash and underscore

Default Value:

blank

Summary of Contents for Touch Pilot 33CNTPILOT

Page 1: ... 2 Decorative Bezel 2 Chiller Display Mounting 2 Operation 4 Power Up Display 4 Default Device Designation 4 Default Group Designation 4 Group Display Screen 4 To Remove a Point from a Group Display 5 To Add a Point to a Group Display 5 Navigation and Operation Pushbuttons 5 BACK 5 HOME 5 MAIN MENU 5 PREVIOUS 5 NEXT 5 OK 5 NO 5 CANCEL 5 CLEAR DATA 5 RESET DATA 5 ADD 5 REMOVE 5 INC DEC 5 SCROLL UP ...

Page 2: ...ii ...

Page 3: ... 24 Vac See Figure 2 on page 3 The power supply is 24 Vac at 60 Hz 15 10 VA minimum NOTE Do not run sensor or communication wiring in the same conduit with line voltage wiring Do not run 24 Vac wiring in the same multi conductor cable used for sensors or communications Perform the following steps to connect the power trans former 1 Install the field supplied transformer in an electrical en closure...

Page 4: ...e Figure 4 on page 3 The assembly will mount directly to the wall requiring only a small hole in the wall allowing the wiring connection to pass through Use four 8 x 1 5 in Phillips panhead screws and four wall anchors to fasten the Display to the wall DECORATIVE BEZEL A decorative bezel is supplied Af ter mounting and wiring the Display snap the decorative bezel on the Display to cover the mounti...

Page 5: ...Wiring 1 2 3 6 5 4 1 2 3 COMM GND 1000 FT MAXIMUM DRAIN WIRE TYP BLK TYP WHT TYP RED TYP BYPASS CONTROLLER ZONE CONTROLLER SYSTEM PILOT ZONE CONTROLLER BRIDGE RECOMMENDED 1 2 3 1 2 3 CCN CCN CCN CCN CHILLER DISPLAY Figure 3 Touch Pilot Bezel Figure 4 Touch Pilot Surface Mounting ...

Page 6: ...FORCETM chiller contains all 8 group displays Going forward more Carrier equipment will support this group functionality Following installation and initial power up the installer should Login and then select the Setup option from the Main Menu to access the display s various setup and con figuration functions Refer to Login and Setup which ap pear in the Main Menu section of this manual Figure 5 E...

Page 7: ...AIN MENU Displays the Main Menu screen A description of all Main Menu options can be found in the Main Menu section of this manual PREVIOUS In a group of sequential screens of the same type moves to the next earlier screen in the group NEXT In a group of sequential screens of the same type advances to the next screen in the group OK Agrees with or says yes to a prompt and performs the appropriate ...

Page 8: ...owing this Main Menu section ATTACH Pressing the Main Menu s button will allow you to display the Attach list where you can select an existing device or add a new device and then establish communication with the selected device The At tach list consists of device name bus and element num bers The first entry in the Attach list surrounded by two is referred to as the Default device It will be the d...

Page 9: ...able screen If the device has multiple tables of that type the Display will show a list of tables from which you can select the one you wish to access As you make changes to values in these tables the new values will be displayed On pressing a Navigation pushbutton to exit the current screen a confirmation mes sage will be displayed Pressing will save and down load the new values to the attached d...

Page 10: ... designation CONFIGURATION TABLES Display operation is controlled by decisions entered in the the following configuration tables which are accessible from a Carrier front end such as the Network Service Tool or ComfortVIEW CtlrID Controller Identification Configuration Table USERCONF User Configuration Table NOTE You should always perform an Upload to obtain the latest configuration before making ...

Page 11: ...Default Value 0 Network Settings Alarm Acknowledger Use this decision to specify whether the Touch Pilot will act as the alarm acknowledger for its CCN There must be only one alarm acknowledger per CCN Therefore if another CCN device such as ComfortVIEW the Autodial Gateway or TeLINK is already set as the Alarm Acknowledger for the CCN then this deci sion should be set to No NOTE The Display must ...

Page 12: ... Value blank Disable START STOP control Equipment Start Stop This decision is used in conjunc tion with the Display s Start Stop button Enter the CCN variable name of the equipment point to which the Start Stop output point is connected If you press the button while in equipment mode the Display will first look at the equipment point s status in accordance with the variable name you entered in the...

Reviews: