background image

8

Table 3 - Setup Menu (continued)

Pressing

Allows you to...

PASSWORDS

configure limited and full logged-in access
system passwords. Note that you must
be logged in with full access to view and
change the passwords. All passwords
must consist of 4-digits, which you can
enter using the numeric keypad.

Access levels and associated privileges
are as follows:

Limited Logged-in Access - provides you
with read/write access to all available
tables (except service configuration tables,
where you will not  be permitted to modify
point data, and Group Display tables,
where you will not be permitted to add
points.) This access level also provides
read/write access to all Display Setup prop-
erties except Display, CCN, and Password.

Full Logged-in Access - provides you
with read/write access to all available
tables for the attached device and all Dis-
play properties.

Note that if you do not log in, you will
have read-only access to all tables in the
attached device. You will be prompted to
log in when attempting to access pass-
word-required functions.

DISPLAY

view data from the Display's Ctlr-ID Table
and specify the Display's Operating
Mode. Equipment mode provides access
only to the Default device or to the de-
vice currently connected to the Display's
RS-485 connector (via the Local Equip-
ment Network (LEN) Bus). Network mode
provides access to all devices on the CCN
Bus connected to the Display's RS-485
connector.
NOTE:  When changing the operating
mode, a power cycle is required in order

for the new operating mode to take effect.

CCN

view and modify the following  CCN data:
address and baud rate, alarm
acknowledger and broadcast
acknowledger designation.

CONFIGURATION TABLES

Display operation is controlled by decisions entered in the
the following configuration tables, which are accessible from
a Carrier front end such as the Network Service Tool or
ComfortVIEW:

CtlrID – Controller Identification Configuration Table

USERCONF – User Configuration Table

NOTE:  You should always perform an Upload to obtain the

latest configuration before making configuration table

changes.

User Configuration (USERCONF) Table –

  The User

Configuration table is shown in Figure 12. Each decision is
explained below.

Backlight Always On? –  Use this decision to indicate
whether to keep the backlight on continuously, or whether
to turn it off after 60 seconds with no activity.

Allowable Entries: No/Yes  (No=0 or Yes=1)
Default Value:

No

Full Access Password – Use this decision to specify the
full access password. Refer to Table 1 - Setup Menu for
additional information on passwords.

Allowable Entries: 0 

through 9999

Default Value:

3333

Limited Access Password – Use this decision to specify
the limited access password.

Allowable Entries: 0 

through 9999

Default Value:

2222

Active Language – Use this decision to specify the Display's
active language. All translatable text will be displayed in
this language.

Allowable Entries: 0 

through 1

Default Value:

0

Time Format –  Use this decision to specify the format for
display of time.

Allowable Entries: 0 = H:MM AM/PM without leading

zero
1 = HH:MM with leading zero when
necessary

Default Value:

0

Date Format –  Use this decision to specify the format for
display of date.

Allowable Entries: 0 = MM-DD-YYYY with leading zero

when necessary
1 = DD-MM-YYYY with leading zero
when necessary
2 = YYYY-MM-DD

Default Value:

0

Units Base  –  Use this decision to specify engineering
units.

Allowable Entries: 0 = U.S.

1 = Metric

Default Value:

0

Contrast Control  –  Use this decision to enable or disable

Summary of Contents for Touch Pilot 33CNTPILOT

Page 1: ... 2 Decorative Bezel 2 Chiller Display Mounting 2 Operation 4 Power Up Display 4 Default Device Designation 4 Default Group Designation 4 Group Display Screen 4 To Remove a Point from a Group Display 5 To Add a Point to a Group Display 5 Navigation and Operation Pushbuttons 5 BACK 5 HOME 5 MAIN MENU 5 PREVIOUS 5 NEXT 5 OK 5 NO 5 CANCEL 5 CLEAR DATA 5 RESET DATA 5 ADD 5 REMOVE 5 INC DEC 5 SCROLL UP ...

Page 2: ...ii ...

Page 3: ... 24 Vac See Figure 2 on page 3 The power supply is 24 Vac at 60 Hz 15 10 VA minimum NOTE Do not run sensor or communication wiring in the same conduit with line voltage wiring Do not run 24 Vac wiring in the same multi conductor cable used for sensors or communications Perform the following steps to connect the power trans former 1 Install the field supplied transformer in an electrical en closure...

Page 4: ...e Figure 4 on page 3 The assembly will mount directly to the wall requiring only a small hole in the wall allowing the wiring connection to pass through Use four 8 x 1 5 in Phillips panhead screws and four wall anchors to fasten the Display to the wall DECORATIVE BEZEL A decorative bezel is supplied Af ter mounting and wiring the Display snap the decorative bezel on the Display to cover the mounti...

Page 5: ...Wiring 1 2 3 6 5 4 1 2 3 COMM GND 1000 FT MAXIMUM DRAIN WIRE TYP BLK TYP WHT TYP RED TYP BYPASS CONTROLLER ZONE CONTROLLER SYSTEM PILOT ZONE CONTROLLER BRIDGE RECOMMENDED 1 2 3 1 2 3 CCN CCN CCN CCN CHILLER DISPLAY Figure 3 Touch Pilot Bezel Figure 4 Touch Pilot Surface Mounting ...

Page 6: ...FORCETM chiller contains all 8 group displays Going forward more Carrier equipment will support this group functionality Following installation and initial power up the installer should Login and then select the Setup option from the Main Menu to access the display s various setup and con figuration functions Refer to Login and Setup which ap pear in the Main Menu section of this manual Figure 5 E...

Page 7: ...AIN MENU Displays the Main Menu screen A description of all Main Menu options can be found in the Main Menu section of this manual PREVIOUS In a group of sequential screens of the same type moves to the next earlier screen in the group NEXT In a group of sequential screens of the same type advances to the next screen in the group OK Agrees with or says yes to a prompt and performs the appropriate ...

Page 8: ...owing this Main Menu section ATTACH Pressing the Main Menu s button will allow you to display the Attach list where you can select an existing device or add a new device and then establish communication with the selected device The At tach list consists of device name bus and element num bers The first entry in the Attach list surrounded by two is referred to as the Default device It will be the d...

Page 9: ...able screen If the device has multiple tables of that type the Display will show a list of tables from which you can select the one you wish to access As you make changes to values in these tables the new values will be displayed On pressing a Navigation pushbutton to exit the current screen a confirmation mes sage will be displayed Pressing will save and down load the new values to the attached d...

Page 10: ... designation CONFIGURATION TABLES Display operation is controlled by decisions entered in the the following configuration tables which are accessible from a Carrier front end such as the Network Service Tool or ComfortVIEW CtlrID Controller Identification Configuration Table USERCONF User Configuration Table NOTE You should always perform an Upload to obtain the latest configuration before making ...

Page 11: ...Default Value 0 Network Settings Alarm Acknowledger Use this decision to specify whether the Touch Pilot will act as the alarm acknowledger for its CCN There must be only one alarm acknowledger per CCN Therefore if another CCN device such as ComfortVIEW the Autodial Gateway or TeLINK is already set as the Alarm Acknowledger for the CCN then this deci sion should be set to No NOTE The Display must ...

Page 12: ... Value blank Disable START STOP control Equipment Start Stop This decision is used in conjunc tion with the Display s Start Stop button Enter the CCN variable name of the equipment point to which the Start Stop output point is connected If you press the button while in equipment mode the Display will first look at the equipment point s status in accordance with the variable name you entered in the...

Reviews: