16
automatically energize the HUM output during a call for humidification. The N.O.
relay contacts will be used to energize the humidifier. See fan powered humidifier
installation instructions for more details.
5. Commissioning
This section addresses initial power up (or commissioning) of a new Infinity
r
Touch Control. The control will communicate and identify all components in the
Infinity
r
System. The following is a typical example for a communicating
variable--speed furnace / fan coil with a 2--stage air--conditioner / heat pump
(including HYBRID HEAT
r
dual fuel system). The process may vary for other
types of systems. See the Infinity System HVAC equipment Installation Instructions
for more details, as provided.
5.1.
Searching for Indoor Unit
The Infinity Touch Control will light up and begin the commissioning process by
displaying “Searching for indoor unit”. This includes Infinity
r
small packaged
products (SPP), with Infinity Touch Wall Control Version 8.0 software or later; and
Infinity System geothermal units with Infinity Touch wall control Version 13
software, or later.
A12177