Once the equipment has been selected, the appropriate menus will be displayed.
6.3.1.
Thermostat
First touch
SETUP
, then touch
THERMOSTAT
to set up the parameters for the
Infinity
r
Touch Control.
A13233
6.3.1.1.
Auto Mode set up
Once the auto changeover option has been selected, touch SAVE.
S
Enable or Disable
: Choose to enable or disable auto changeover mode
d
Default = Enable
S
Auto changeover time
: Adjustable from 5 to 120 minutes
d
Default = 30 minutes
6.3.1.2.
Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. The deadband does not change when the user changes between
Fahrenheit (
_
F) and Celsius (
_
C). Ex: A 2
_
deadband will be 2
_
F or 2
_
C and does