29
not change with units,
_
F and
_
C. This can allow one setting to “push” the other to
maintain this difference. When the correct deadband is set, touch
SAVE
.
S
Deadband
: Adjustable from 0 to 6
_
d
Default = 2
_
6.3.1.3.
Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. When the correct offsets are made, touch
SAVE
.
S
Outdoor temperature:
Adjustable from --5 to 5
_
F (--3 to 3
_
C)
d
Default = 0
_
F
S
Humidity:
Adjustable from --10 – 10%
d
Default = 0%
6.3.1.4.
Reset factory defaults
This option allows the installer to reset certain factory parameters. After the
selections are made, touch
SAVE
.
S
Program Schedule:
Reset back to pre--programmed time and temperature.
S
User Settings:
Reset user settings back to pre--programmed values.
S
Install Settings:
Reset installation settings back to pre--programmed values.
S
Last 10 Faults:
Reset the last 10 system faults under the Service menu.
6.3.1.5.
Scheduling Enable
This option lets the installer allow programming features. After the selection is
made, touch
SAVE
.
S
Scheduling:
On or Off
d
Default = On